Connectivity Module

Installation 1-2

How to Install the Connectivity Module for a stand-alone Power Manager or Digital Power Meter

The Connectivity Module (CM) mounts on a DIN rail near the Power Manager (PM) or Digital Power Meter (DPM). A long serial cable connects the Connectivity Module to the PM or DPM. Refer to installation drawings provided and follow the steps below to install the Connectivity Module.

Connectivity Module Kit K889958

for a stand-alone Power Manager or Digital Power Meter (not connected to an ATS)

Connectivity

Module 5150

DIN Rail and

Hardware

4 ft. Serial Cable

for PM or DPM

!DANGER

To avoid possible shock, burns, or death, deenergize all electrical sources to the ATS before installing the Connectivity Module.

1.De-energize the power source that feeds the PM (or DPM). Open enclosure door and check with a non-contact AC voltage detector.

2.Mount the DIN rail (supplied in the kit) onto two studs (on the door) below or adjacent to the PM or DPM.

3.Install Connectivity Module onto DIN rail by hooking the bottom of module on bottom of DIN rail and rocking it upward unit it snaps in place.

4.Install the 4-foot serial cable between the Power Manager J5 receptacle (or Digital Power Meter J2 receptacle) and the Connectivity Module J2 receptacle.

Now test communications (go to next column).

How to Test Communication to the Connectivity Module

You need the following settings from your network administrator for each Connectivity Module (CM) connected to an Automatic Transfer Switch (ATS), Power Manager (PM), or Digital Power Meter (DPM). Fill in the form provided in the Appendix:

IP Address: ______________ (unique for each module)

Subnet mask __________ (usually same for all modules)

Gateway: ________________________ (usually blank)

Required items:

Portable laptop computer with network card, running Windows Xp and Windows Internet Explorer 6.0 + installed.

Ethernet crossover network cable (part no. 629590-006).

Connectivity Module connected to the ATS, PM, or DPM.

1.Directly connect the specified Ethernet crossover cable between your laptop’s Ethernet jack and the deenergized Connectivity Module jack J3.

2.For safety, close the ATS, PM, or DPM enclosure door as far as possible (with the crossover cable running to the laptop computer outside the enclosure). Then energize ATS, PM, or DPM and the Connectivity Module.

3.Refer to the Appendix and select the appropriate TCP/IP Installation & Configuration instructions for your laptop computer’s operating system. This procedure sets up your laptop computer (if necessary) for network connections and tests communications to the Connectivity Module.

4.After you have confirmed communication with the Connectivity Module, continue to the next page to view and change the configuration of the Connectivity Module and ATS, PM, or DPM.

Now view and change the configuration

(go to page 1-3)