Connectivity Module

7000 & 4000 Series ATSs 2-1

Device Configurator Screen for 7000 & 4000 Series ATSs

The Device Configurator Screen for 7000 & 4000 Series ATSs shows the Group 5 controller configuration settings (right side) and Connectivity Module (server) configuration settings (left side) for the selected ATS.

Group 5 Controller Configuration (right side)

Enter or change the ATS Name (8 char. max.)and the ATS Location (20 char. max.). Press the Update button when finished to save the controller configuration changes.

Connectivity Module (server) Configuration (left side)

Several configuration settings must be set appropriately as described below. Press the Update Server button when finished to save configuration changes.

Consult with your network administrator for these 4 settings:

IP Address

Subnet Mask

Gateway Address

TCP Port Number

(Range of ports allowed is:

10024-65535, but do not use

ports 14000-14009 or 30718)

Serial Port Speed 19200

Flow Control No flow control

Interface Mode RS485-4 or 2 Wire

Encyrption enable check box and assign an AES port (same range as TCP port but do not use the same port number used for TCP port.)

3rd party device running own protocols

SNMP refer to Appendix A-5

ATS Name

ATS Location

Press Update button when finished to save the configuration changes. Do this before you press Update Server button.

After Controller has been updated, press Update Server button to save the configuration changes.

Device Configurator Screen for 7000 & 4000 Series ATSs

When a Power Manager or Digital Power Meter is connected, additional buttons appear at the bottom of the Connectivity Module Device Configuration screen.

Press to configure the Power

Manager or Digital Power Meter.

Press to configure the Group 5 Controller.

After Controller, PM, or DPM has been updated, press Update Server button to save the configuration

Additional Buttons on Device Configurator Screen for

7000 & 4000 Series ATSs with Power Manager or Digital Power Meter

Page 13
Image 13
Emerson 5100 Device Configurator Screen for 7000 & 4000 Series ATSs, Connectivity Module 7000 & 4000 Series ATSs