Connectivity Module ASCO 940/962 ATSs 4-1
Device Configurator Screen for ASCO 940/962 ATSs
The Device Configurator Screen for ASCO 940/962 ATSs shows the Group 7A controller configuration
settings (right side) and the Connectivity Module (server) configuration settings (left) for the selected ATS.
Group 7A Controller Configuration (right side)
Enter or change the ATS Name (18 char. max.) and ATS Nominal Voltage (must be entered to get correct
reading). Press the Update button when finished to save the Group 7A controller configuration changes.
Connectivity Module (server) Configuration (left side)
Several configuration settings must be set appropriately as described below. Press the Update Server button
when finished to save configuration changes.
Device Configurator Screen without Power Manager
Device Configurator Screen with Power Manager
Nom. Volta
g
eATS Name
Serial Port Speed 9600
Consult with your network
administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
10024-65535, but do not use
ports 1400-14009 or 30718)
Press Update button
when finished to save
the configuration
Press Update Server button
when finished to save the
configuration changes.
Flow Control No flow control
Interface Mode RS485-4 or 2 Wire
Nom. Volta
g
e
A
TS Name
Serial Port S
p
eed 9600
Consult with your network
administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
10024-65535, but do not use
ports 1400-14009 or 30718)
Press Update button
when finished to save
the configuration
Press Update Server button
when finished to save the
configuration changes.
Flow Control No flow control
Interface Mode RS422/485-4Wire
Encyrption enable check box and
assign an AES port (same range as
TCP port but do not use the same
port number used for TCP port.)
Encyrption enable check box and
assign an AES port (same range as
TCP port but do not use the same
port number used for TCP port.)
xxx
xxx