4.0MAJOR COMPONENTS

The Liebert GXT2-10000RT208 is composed of three major assemblies to provide easier handling, installation and versatility.

4.1Main Frame and Electronics

This 6U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The UPS is shipped with standard hardwire terminal blocks for input and output connections.

Figure 1 10 kVA Dual Inverter Liebert GXT2-10000RT208, front and rear views

Status Indicators

and Controls

FRONT VIEW

Front Bezels, 3

 

External Battery

Connectors

 

Output

 

Circuit

GXT

Breaker

UPStation

 

Hardwire

Knockouts

Battery Compartment

(behind center and right bezels); Internal

Battery Pack is shipped loose

(see Section 4.2)

REAR VIEW

Liebert

 

IntelliSlot® Port

DB-9

Communications

Ports, 2

Cooling Fan,

1 of 3

REPO

Switch

UPS/Bypass

Breaker

Input Circuit

Breaker

4.2Internal Battery Pack

The center front bezel may be pulled forward and removed to reveal the battery access plate. The cover plate can be removed by extracting the three screws at the top of the cover plate and lifting the plate off. The two internal battery packs are compact assemblies ready to slide into the battery com- partment after the front battery access plate has been removed. Electrical connection is made with the two slotted battery connectors.

Figure 2 Internal battery pack and connector

Battery connector

on front of battery pack