Specifications

14.0SPECIFICATIONS

Table 7

UPS specifications

 

 

 

 

 

 

Model Number

 

Liebert GXT2-10000RT208

 

 

 

 

 

 

 

8000W/8660VA at 127/220 (120 or 240 degrees only)

 

 

 

8000W/8660VA at 120/208 (120 or 240 degrees)

 

Model Rating

 

8000W/10000VA at 120/240 (180 degrees)

 

 

8000W/10000VA at 115/230 (180 degrees only)

 

 

 

 

 

 

7200W/9000VA at 110/220 (180 degrees only)

 

 

 

6400W/8000VA at 100/200 (180 degrees only)

DIMENSIONS, RACK MOUNT, W x D x H

 

 

Unit, in. (mm)

 

16.93 x 25.98 x 10.5 (430 x 660 x 267); 6U

 

Shipping, in. (mm)

 

22.44 x 33.86 x 15.75 (570 x 860 x 400)

WEIGHT lb (kg)

 

 

Unit

 

109 (49.3)

 

Shipping

 

118 (53.6)

INPUT AC PARAMETERS

 

 

Nominal Operating Frequency

 

50 or 60 Hz (Factory Default = 60)

 

Factory Default VAC

 

120/208 VAC at 120 degrees

L1-L2 Factory Default Input Phase

 

120 degrees

 

Angle

 

 

 

 

 

Allowable Input Phase Angle

 

120, 180, 240 degrees, Auto-sensing on application of AC

 

 

(Restrictions for L-N voltages other than 120 VAC)

 

 

 

Factory Default L1-N, L2-N VAC

 

120 VAC nominal

User Configurable L1-N, L2-N VAC

 

100/110/115/120/127 VAC (May be modified using configuration program)

L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)

 

100% - 91% loading

 

100 VAC - 140 VAC

 

90% - 71% loading

 

90 VAC - 140 VAC

 

70% - 51% loading

 

80 VAC - 140 VAC

 

50% - 31% loading

 

70 VAC - 140 VAC

 

30% - 0% loading

 

60 VAC - 140 VAC

L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)

 

100% - 91% loading

 

90 VAC - 140 VAC

 

90% - 71% loading

 

80 VAC - 140 VAC

 

70% - 51% loading

 

70 VAC - 140 VAC

 

50% - 0% loading

 

60 VAC - 140 VAC

L1-N, L2-N Max. Allowable VAC

 

150 VAC

 

Input Frequency w/o Battery

 

40 - 70 Hz

 

Operation

 

 

 

Input Power Connection

 

Hardwire Terminal Block 3W + G (L-L-N-G)

OUTPUT AC PARAMETERS

 

 

Factory Default VAC

 

120/208 VAC @ 120 degrees

 

L1-L2 Factory Default

 

120 degrees

 

Output Phase Angle

 

 

 

 

 

Allowable Output Phase Angle

 

120, 180, 240 degrees Auto-sensing on initial application of input AC

Factory Default L1-N, L2-N VAC

 

120 VAC nominal

User Configurable L1-N, L2-N VAC

 

100/110/115/120/127 VAC, ±2%

 

Output Connections

 

Hardwire Terminal Block 3W + G (L-L-N-G);

 

 

also see 7.2 - Output Receptacle Distribution Options

 

 

 

 

Frequency

 

50 Hz or 60 Hz, Nominal

 

Waveform

 

Sinewave

 

Main Mode Overload

 

130% for 60 seconds; 200% for 5 seconds with transfer to bypass.

44

Page 50
Image 50
Emerson GXT2-10000RT208 user manual Specifications, UPS specifications