Specifications

Table 13 External battery cabinet specifications

Model Number

GXT2-288RTVBATT

 

 

Used w/ UPS Model

Liebert GXT2-10000RT208

 

 

DIMENSIONS, Rack Mount, W x D x H

 

 

Unit (with bezel), in (mm)

16.93 x 25.98 x 7 (430 x 660 x 178); 4U

 

 

Shipping, in (mm)

22.64 x 33.46 x 12.40 (575 x 850 x 315)

 

 

WEIGHT lb (kg)

 

 

 

Unit

41.6 (18.9)

 

 

Shipping

50.6 (23)

 

 

BATTERY PARAMETERS

 

 

 

Type

Valve-regulated, non-spillable, flame retardant, lead acid

 

 

Qty x V x Rating

(2) x 12 x 12V x 9.0 AH

 

 

Battery Manufacturer / Part #

Yuasa / REW 45-12 FR

 

 

Backup Time

See Table 6 - Battery run times

 

 

ENVIRONMENTAL

 

 

 

Operating Temp

+32°F to +104°F (0°C to +40°C)

 

 

Storage Temp

+5°F to +122°F (-15°C to +50°C)

 

 

Relative Humidity

0% to 95%, non-condensing

 

 

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

 

 

Storage Elevation

50,000 ft. (15,000m) maximum

 

 

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed (suitable for computer room applications)

 

 

RFI/EMI

FCC Part 15, Subpart B, Class A

 

 

Transportation

ISTA Procedure 1A

 

 

14.1Product Warranty Registration

To register for warranty protection:

Visit the Quick Links section of our Website at: http://www.liebert.com

Click on Product Warranty Registration and fill in the form.

If you have any questions, please contact us at:

US: 800-222-5877

Outside the US: 614-841-6755

upstech@emersonnetworkpower.com

Contact Liebert Global Services at:

US: 800-LIEBERT (800-543-2378) powertech@emersonnetworkpower.com

47

Page 53
Image 53
Emerson GXT2-10000RT208 user manual Product Warranty Registration, External battery cabinet specifications, Model Number