Emerson GXT2-10000RT208 Connect Input/Output Power, Distribution Module Electrical Connections

Models: GXT2-10000RT208

1 56
Download 56 pages 13.81 Kb
Page 20
Image 20

Installation and Configuration

6.3Connect Input/Output Power

The UPS has hardwire terminal blocks for input and output electrical connections. Optional output distribution modules permit connecting additional loads to the UPS. These optional plug-and-play distribution modules offer different types and numbers of connection plugs.

! WARNING

The UPS must be completely powered down before beginning to make these electrical connections.

6.3.1Distribution Module Electrical Connections

Electrical connections are made through a removable conduit box that attaches to the rear of the UPS.

The installer must provide a 60A branch circuit breaker. The input circuit breaker and the output cir- cuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and the distribution box.

The manual bypass switch passes utility power directly to the bypass switch from the input terminal block. The input circuit breaker does not disconnect power from the manual bypass switch.

Figure 6 60A branch circuit breaker connection diagram

Utility

60A External

Branch

Circuit Breaker

UPS

60A 60A Input Output Circuit Circuit Breaker Breaker

60A Maintenance

Bypass Breaker

Input Output Indicator Indicator

Input

Output

Terminal

Block

Optional

Output

Distribution

Plate

! CAUTION

A disconnect switch shall be provided by others for ac input circuit. To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.

! CAUTION

A disconnect switch shall be provided by others for ac output circuit. To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.

14

Page 20
Image 20
Emerson GXT2-10000RT208 user manual Connect Input/Output Power, Distribution Module Electrical Connections