Troubleshooting
Table 5 | Troubleshooting guide |
| ||
|
|
| ||
Problem | Cause | Solution | ||
|
|
|
| |
UPS fails to start when the | UPS is | Ensure the UPS is OFF. Disconnect all loads and ensure | ||
nothing is lodged in output receptacles. | ||||
ON button is pressed. | overloaded. | |||
Ensure the loads are not defective or shorted internally. | ||||
|
|
| ||
|
|
|
| |
|
| UPS not plugged in. | UPS is operating in Battery Mode, make certain UPS is | |
|
| securely plugged into the wall receptacle. | ||
|
|
| ||
Battery indicator is | UPS input protection fuse | UPS is operating in Battery Mode. Save data and close | ||
has blown/opened. | applications. Replace UPS input fuse, then restart UPS. | |||
illuminated. |
| |||
|
| Utility voltage out of UPS | UPS is operating in Battery Mode. Save data and close | |
|
| applications. Ensure utility supply voltage is within | ||
|
| input range. | ||
|
| acceptable limits for UPS. | ||
|
|
| ||
|
|
|
| |
|
| Batteries are not fully | Keep UPS plugged in continuously at least 24 hours to | |
|
| charged. | recharge batteries. | |
UPS has reduced battery | UPS is overloaded. | Check load level display and reduce the load on the UPS. | ||
time. |
|
|
| |
| Batteries may not be able to | Replace batteries. Contact your local dealer, Liebert | ||
|
| |||
|
| representative or the Liebert Worldwide Support Group for | ||
|
| hold a full charge due to age. | ||
|
| replacement battery kit. | ||
|
|
| ||
|
|
| ||
Fault and Bypass indicators | UPS overloaded or load | Check load level display and remove | ||
and all Load Level indicators | Recalculate the load and reduce number of loads | |||
equipment is faulty. | ||||
are illuminated. | connected to UPS. Check load equipment for faults. | |||
| ||||
|
|
| ||
Fault and Bypass indicators | UPS control power supply | UPS requires service. Contact your local dealer, Liebert | ||
and diagnostic indicator C are | ||||
fault. | representative or the Liebert Worldwide Support Group. | |||
illuminated. |
| |||
|
|
| ||
|
|
| ||
Fault and Bypass indicators | UPS PFC (Power Factor | UPS requires service. Contact your local dealer, Liebert | ||
and diagnostic indicator D are | ||||
Correction Circuit) fault. | representative or the Liebert Worldwide Support Group. | |||
illuminated. |
| |||
|
|
| ||
|
|
|
| |
|
| UPS internal fan has a | Ensure the UPS is not overloaded, ventilation openings | |
|
| are not blocked and room ambient temperature is not | ||
Fault and Bypass indicators | problem or UPS shutdown | |||
excessive. | ||||
and diagnostic indicator A are | due to temperature | |||
Wait 30 minutes to allow UPS to cool, then restart UPS. | ||||
illuminated. |
| condition. Load is on bypass | ||
| If UPS does not restart, contact your local dealer, Liebert | |||
|
| power. | ||
|
| representative or the Liebert Worldwide Support Group. | ||
|
|
| ||
|
|
| ||
Fault and Bypass indicators | UPS internal DC bus | UPS requires service. Contact your local dealer, Liebert | ||
and diagnostic indicator B are | ||||
overvoltage. | representative or the Liebert Worldwide Support Group. | |||
illuminated. |
| |||
|
|
| ||
|
|
| ||
Fault and Bypass indicators |
| UPS requires service. Contact your local dealer, Liebert | ||
and diagnostic indicator E are | UPS inverter fault. | |||
Representative or the Liebert Worldwide Support Group. | ||||
illuminated. |
|
| ||
|
|
| ||
|
|
| ||
Fault and Bypass indicators | UPS requires service. Contact your local dealer, Liebert | |||
and diagnostic indicators A | ||||
Communications Failure | Representative or the Liebert Worldwide Support Group. | |||
and B are illuminated. | ||||
|
| |||
|
|
| ||
Fault indicator and diagnostic |
| Replace batteries. Contact your local dealer, Liebert | ||
indicators A and C are | UPS failed the battery test. | |||
representative or the Liebert Worldwide Support Group. | ||||
illuminated. |
|
| ||
|
|
| ||
|
|
|
| |
|
|
| Only phase angles of 120, 180 or 240 degrees | |
|
|
| (±10 degrees) are permitted. These must be compatible | |
|
|
| with the selections in the configuration program. | |
|
|
| Or the phase angle has changed while the UPS was | |
Fault indicator and diagnostic | L1 to L2 phase angle | running. The phase angle is detected at startup and | ||
cannot be changed to a different power source while | ||||
indicators A and D are | ||||
unacceptable. | running. | |||
illuminated. |
| |||
|
| Turn the UPS Off and wait until the fans stop. Apply input | ||
|
|
| ||
|
|
| AC power. The UPS will reprogram the phase angle to | |
|
|
| match the utility, if the utility is 120, 180 or 240 degrees | |
|
|
| between L1 and L2. If this does not resolve the issue, | |
|
|
| contact a qualified electrician to verify the site wiring. |