Emerson GXT2-10000RT208 user manual Install the Internal Battery Packs

Models: GXT2-10000RT208

1 56
Download 56 pages 13.81 Kb
Page 23
Image 23

Installation and Configuration

6.4Install the Internal Battery Packs

To facilitate shipping and installation, the Liebert GXT2-10000RT208 ships without the internal bat- tery packs installed. Once the UPS is installed in place, the internal battery packs must be installed.

L

ie

b

e

r t

 

 

 

 

!

Controls and Indicators (horizontal overlay)

Mjfcfsu

!

Battery Compartment

Battery

 

Battery

 

Bracket

Battery

Front

Bezel

Connector

 

Battery

Cover

Front of Battery

1.Unpack the two internal battery packs from their shipping container.

2.Lift one battery pack from its packaging, holding it in the center of the pack.

3.Align the battery pack so that the cable is at the top right closest to the power module in the frame.

4.Slip the back of battery pack into the battery compartment and slide it in until the battery reaches the back of the UPS.

5.Install the battery bracket on the front of the battery pack with two screws.

6.Connect the two slotted connectors and tuck the wires in around the battery pack handles.

7.Repeat for the second battery pack.

8.Install the battery cover grille, tightening the three screws.

9.For tower installation, place the vertical overlay over the controls and indicators (see Figure 8).

10.Install the two front bezels.

17

Page 23
Image 23
Emerson GXT2-10000RT208 user manual Install the Internal Battery Packs, Controls and Indicators horizontal overlay