Troubleshooting

13.0TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the Liebert GXT2-10000RT208 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.

1.The Fault indicator will illuminate, indicating the UPS has detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

3.One or more additional Load Level/Battery Level indicators will be illuminated to provide a diagnostic aid to the operator, as described below:

A B C

AC Input indicator

D E

Fault indicator

Battery indicators

Load Level indicators

Bypass indicator

 

 

Battery indicator UPS ON indicator

Table 3

Fault indicators

 

 

Indicator status

Diagnosis/Audible alarm

 

 

All indicators

On bypass due to output overload; beep every half-second

 

 

 

Indicator A

 

On bypass due to overtemperature condition

 

 

 

Indicator B

 

On bypass due to DC bus overvoltage

 

 

 

Indicator C

 

On bypass due to control power supply failure

 

 

 

Indicator D

 

On bypass due to PFC failure

 

 

 

Indicator E

 

On bypass due to inverter failure

 

 

Indicators A&B

Inverter-to-Inverter communications failure; half-second beep every 1 second

 

 

Indicators A&C

UPS failed battery test; 2-second beep every 60 seconds

 

 

Indicators A&D

L1 to L2 phase angle unacceptable

 

 

Indicators B&C

REPO is currently activated, UPS output cannot be started by any method

 

 

 

 

 

UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power

Indicators B&D

is restored, press the OFF button twice within four seconds (to clear the alarm), then

 

 

press the ON button to start UPS (Auto-restart is NOT possible).

Indicators C&E

UPS shutdown due to command from communications (RS232 or SNMP); no beep

 

 

Indicators D&E

UPS is OFF due to charger overvoltage; 1-second beep every 4 seconds

 

 

AC Input indicator On &

On bypass due to the power module cover plate being removed or the slide bracket

Indicators A&C&E

moved from Manual Bypass switch

AC Input indicator On &

AC input has been applied to start UPS but the batteries are either missing or below

Battery indicator Flashing

the minimal level to allow the UPS to start; continuous audible alarm

Bypass indicator Flashing

Bypass voltage is present, but is disabled for use because the voltage or frequency is

outside acceptable limits

 

 