Specifications

Table 7

UPS specifications (continued)

 

 

 

 

 

 

 

Model Number

 

 

Liebert GXT2-10000RT208

 

 

 

 

 

Bypass Protection Limits

 

 

 

 

 

Disable Bypass Operation

If input voltage exceeds ±15% of the nominal voltage

 

Re-enable Bypass Operation

If input voltage returns to within ±10% of nominal output voltage

 

Disable Bypass Operation

When the input frequency prevents synchronous operation

ENVIRONMENTAL

 

 

 

 

 

Operating Temp

+32°F to +104°F (0°C to +40°C)

 

Storage Temp

+5°F to +122°F (-15°C to +50°C)

 

Relative Humidity

0% to 95%, non-condensing

 

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

 

Storage Elevation

50,000 ft. (15,000 m) maximum

 

Audible Noise

<55 dBA, at 1 meter

AGENCY

 

 

 

 

 

 

 

Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

 

 

RFI/EMI

FCC Part 15, Subpart B, Class A

 

Surge Immunity

IEEE/ANSI C62.41 Category A & B

 

Transportation

ISTA Procedure 1A

Table 8

Battery specifications

 

 

 

 

 

 

 

Model Number

 

 

GXT2-288RTBKIT—Two Required

 

 

 

 

 

 

DIMENSIONS, W x D x H

 

 

 

 

 

Shipping, in. (mm)

 

 

11.02 x 24.02 x 15.35 (280 x 610 x 390)

 

 

 

 

 

 

WEIGHT lb (kg)

 

 

 

 

 

Unit

 

 

78.1 (35.5)

 

 

 

 

 

 

 

 

Shipping

 

 

83.6 (38)

 

 

 

 

 

 

 

Type

 

Valve-regulated, non-spillable, flame retardant, lead acid

 

 

 

 

 

 

 

 

Quantity x V x Rating

 

 

(2) x 12 x 12V x 9.0 AH

 

 

 

 

 

 

Battery Manufacturer / Part #

 

 

Yuasa / REW 45-12 FR

 

 

 

 

 

 

 

 

Back-Up Time

 

 

See Table 6 - Battery run times

 

 

 

 

 

 

 

Recharge Time

 

6 Hours to 90% capacity after full discharge into 100% load

 

 

 

 

 

Table 9

Optional output distribution specifications—PD-101

 

 

 

 

Model Number

 

 

PD-101

 

 

 

 

 

 

DIMENSIONS, W x D x H

 

 

 

 

 

 

 

 

 

 

 

Shipping, in. (mm)

 

 

8.86 x 10.43 x 7.87 (225 x 265 x 200)

 

 

 

 

 

 

WEIGHT lb (kg)

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

3.8 (1.7)

 

 

 

 

 

 

 

 

Shipping

 

 

5.1 (2.3)

 

 

 

 

 

ELECTRICAL SPECIFICATIONS

 

 

 

 

 

 

 

 

 

Amp Rating

 

 

60 Amps

 

 

 

 

 

 

Input Power Connections

 

 

Internal Anderson connectors

 

 

 

 

 

 

Output Power Connection

 

 

 

 

 

 

 

 

 

 

 

L1-L2-G

 

 

(2) L6-30R on a 300mm cord

 

 

 

 

 

 

L1-N-G

(4) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers

 

 

 

 

 

 

L2-N-G

(4) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers

 

 

 

 

 

 

 

45

Page 51
Image 51
Emerson GXT2-10000RT208 Battery specifications, Optional output distribution specifications-PD-101, See Battery run times