Troubleshooting

Using the configuration program, the user may specify the number of GXT2-288VBATT external bat- tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.

Table 6 shows estimated run times at different loads.

Table 6 Battery run times

Battery/External

 

10000VA Run Time

Cabinets

Load%

in Minutes

 

10%

107

 

20%

52

 

30%

31

 

40%

22

Internal Battery

50%

16

60%

13

 

 

70%

10

 

80%

9

 

90%

7

 

100%

6

 

10%

251

 

20%

118

 

30%

74

Internal Battery

40%

52

50%

39

+ 1 External Battery

60%

32

Cabinet

 

70%

26

 

80%

22

 

90%

19

 

100%

17

 

10%

333

 

20%

216

 

30%

118

Internal Battery

40%

85

50%

66

+ 2 External Battery

60%

53

Cabinets

 

70%

44

 

80%

38

 

90%

32

 

100%

28

 

10%

494

 

20%

265

 

30%

191

Internal Battery

40%

119

50%

92

+ 3 External Battery

60%

75

Cabinets

 

70%

62

 

80%

54

 

90%

47

 

100%

41

 

10%

590

 

20%

295

 

30%

236

Internal Battery

40%

178

50%

119

+ 4 External Battery

60%

98

Cabinets

 

70%

82

 

80%

71

 

90%

61

 

100%

54

Battery/External

 

10000VA Run Time

Cabinets

Load%

in Minutes

 

10%

548

 

20%

284

 

30%

217

Internal Battery

40%

151

50%

107

+ 1 LRT Battery

60%

86

Pack

 

70%

66

 

80%

55

 

90%

47

 

100%

40

 

10%

1030

 

20%

538

 

30%

332

Internal Battery

40%

269

50%

231

+ 2 LRT Battery

60%

195

Pack

 

70%

158

 

80%

125

 

90%

109

 

100%

96

 

10%

1473

 

20%

821

 

30%

520

Internal Battery

40%

382

50%

289

+ 3 LRT Battery

60%

264

Pack

 

70%

238

 

80%

215

 

90%

189

 

100%

165

 

10%

1973

 

20%

1053

 

30%

672

 

40%

515

Internal Battery

50%

406

+ 4 LRT

60%

304

 

70%

280

 

80%

263

 

90%

243

 

100%

224

42

Page 48
Image 48
Emerson GXT2-10000RT208 user manual Battery run times, Battery/External 10000VA Run Time Cabinets Load% Minutes