SPECIFICATIONS

Instruction Manual

IM-106-4050 Original Issue March 2006

OxyBalance Oxygen Display and Averaging System

SPECIFICATIONS

Specifications for the OxyBalance system are listied in Table 1-2.

Table 1-2. OxyBalance Specifications

SPECIFICATIONS(1)

Ambient Environment

Temperature specification

Ambient temperature effect on electronics Vibration

Shock

Enclosure

Area Classification

Power Requirements

MicroLogix 1200

Resistive Load on Current Output Input Impedance for Current Terminal

PanelView Plus 600

Minimum On-State Current Nominal On-State Current Maximum On-State Current Current per Group Common 240V ac (Maximum Volts) 120V ac (Maximum Volts) 125V dc (Maximum Volts) 24V dc (Maximum Volts)

I/O

Signal Inputs

Signal Outputs

Signal Output Resolution (for averages) Signal Output Resistive Load Discrete Inputs

Relay Outputs

Architecture

Logic

Individual probes removed from average if

Signal Security

Personnel Security

Color Graphic Display

Size

Type

Resolution

23oF to 149o F (-5oC to 65oC)

Less than .01% of reading per 10oC

IEC 68-2-6 and ISA S37.3

IEC 68-2-31 and ISA S37.3

NEMA 4X

General Purpose

100-240 VAC, 50/60 Hz

0 to 500 Ohms (includes wire resistance)

275 Ohms

2.0mA at 10V dc

8.9mA at 24V dc

12. mA at 30V dc

8A

2.5A(2) (Amperes Continuous)

2.5A(2) (Amperes Continuous)

1.0A (Amperes Continuous)

2.0A (Amperes Continuous)

4-20 mA (qty. 1 to 8 O2 probes)

4-20 mA (qty, 1 to 8 pass through each probe, qty. 4 programmable averages)

12 bit

Less than 500 ohms

"IN CAL" (qty. 2 to 8 from individual probes)

"LOSS OF PLC"

"AVERAGE WARN" if one or more probes drop out of an average. "AVERAGE FAILED" for each average when only one probe in the average remains valid.

Each probe utilizes its own autonomous conditioning electronics, including its own power supply. Any failure in the OxyBalance system will not affect the individual 4-20 mA signals going to the control room for each probe.

4 programmable averages from 2-8 probes

1.) Probe fails (4-20 mA to default condition of 3.5 mA or 21 mA

2.) Probe is in cal (SPS / IMPS contact, must share with control room)

4-20 mA signals to be wired in series to the PLC and to the DCS I/O marshalling panel such that the loss of the PLC will not affect the transmission of the individual probe signals to the DCS. If PLC power, I/O cards or processor card(s) are lost, 4-20 mA signals from the probes are still transmitted to the control room.

Password protection configuration changes in programmable averages.

6" diagonal

Color Active Matrix, TFT LCD

320 by 240 min. Touch screen operator interface

(1)Specifications are subject to change without notification. Our policy is one of continuous improvement and we reserve the right to change specifications.

(2)1.5A above 40oC.

1-5