Instruction Manual

IM-106-4050 Original Issue March 2006

PanelView Removal

Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock and/or damage to the equipment.

NOTE

Make sure to record the wiring connections and locations before disconnecting any wiring. This will aid in the installation of the unit.

1.Disconnect the three power wires from the wire contacts (L1, L2N, and ground) of the PanelView Plus 600, see Figure 5-1.

2.Remove the communications cord from the PanelView Plus 600.

3.Turn mounting levers to the unlocked position, and remove the mounting levers from the mounting lever slots. See Figure 5-3.

4.Carefully slide the PanelView Plus 600 unit through the front of the panel cutout.

Figure 5-1. PanelView System

Wiring

Communications

Cable

38370010

Power Manual background Connection

5-2