Instruction Manual
OxyBalance Oxygen Display and Averaging System
MICROLOGIX 1200 PROGRAMMABLE CONTROLLERS
The MicroLogix 1200 Programmable Controllers consist of one PLC unit and three I/O modules. The PLC mounts horizontally with the expansion I/O modules extending to the right of the controller.
This equipment is intended for use in clean, dry environments where only
Electrostatic discharge can damage semiconductor devices inside the controller. Do not touch connector pins and other sensitive areas.
PLC Removal
Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock and/or damage to the equipment.
NOTE
Make sure to carefully record the wiring connections and locations before disconnecting. This will aid in the installation of the unit.
1.Tag and disconnect all wiring from the MicroLogix PLC.
2.Remove the cover from the ribbon cable connector on the PLC. Use the pull loop on the connector to disconnect the ribbon cable from the PLC. Do not pull on the ribbon cable. See Figure
3.Place a
4.Repeat step 3 for the second DIN rail tab.
5.Pull the bottom of the PLC out and away from DIN Rail, as shown in Figure