C H A P T E R 5 : E T H E R N E T / I P P R O T O C O L

5 . 2 . 2 O n D e m a n d N o d e 0 1 C o n f i g u r a t i o n P a g e

The OnDemand Node 01 Configuration Page

Use this page to modify the settings for Node 01.

Controller Settings

5Select the Controller Type from the drop-down menu. The Controller Type (in this case) specifies the type of PLC that will be communicating with the HS500E.

6Enter the Controller’s IP address. Controller IP address is the IP address assigned to the PLC.

7Enter the Controller’s Slot Number (0-255). Controller Slot Number indicates where in the PLC rack the controller module is installed; normally slot 0 for ControlLogix.

Write Settings

8Specify the number of words (between 1 and 100, 0 = disabled) for the Max Write Size. The Max Write Size value represents the maximum number of 2- byte “words” that the HS500E will attempt to write to PLC memory during each command-response cycle. Note: the actual data size required on the PLC is 3 words larger than the value specified in this field.

H S 5 0 0 E – O P E R A T O R ’ S M A N U A L

P / N : 1 7 - 1 3 0 5 R E V 0 2 ( 1 2 - 0 5 )

 

P A G E 4 2 O F 8 2