FS-8700-19_Metasys_N2 Driver Manual

 

 

 

Page 43 of 51

 

 

 

 

 

 

 

 

 

 

 

 

 

General dynamic Parameters

 

 

Relative Item

Signal Condition

Read/Write

 

Johnson Tag

 

Description

 

 

86

Byte

R/W

 

PM5I@3

 

Input Connection I3@

 

 

87

FP

R/W

 

PM5TYP

 

Options

 

 

88

FP

R/W

 

PM5K2

 

Constant K2

 

 

89

FP

R/W

 

PM5K3

 

Constant K3

 

 

90

FP

R/W

 

PM5K4

 

Constant K4

 

 

91

FP

R/W

 

PM5K5

 

Constant K5

 

 

92

FP

R/W

 

PM5K6

 

Constant K6

 

 

93

FP

R/W

 

PM5K7

 

Constant K7

 

 

94

FP

R/W

 

PM6K1

 

Constant K1 Module #6

 

 

95

Byte

R/W

 

PM6I@1

 

Input Connection I1@

 

 

96

Byte

R/W

 

PM6I@2

 

Input Connection I2@

 

 

97

Byte

R/W

 

PM6I@3

 

Input Connection I3@

 

 

98

FP

R/W

 

PM6TYP

 

Options

 

 

99

FP

R/W

 

PM6K2

 

Constant K2

 

 

100

FP

R/W

 

PM6K3

 

Constant K3

 

 

101

FP

R/W

 

PM6K4

 

Constant K4

 

 

102

FP

R/W

 

PM6K5

 

Constant K5

 

 

103

FP

R/W

 

PM6K6

 

Constant K6

 

 

104

FP

R/W

 

PM6K7

 

Constant K7

 

 

 

 

 

 

 

 

 

 

 

Input Output Config Parameters

 

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

 

105

Word

Read

 

VER

 

Firmware Version

 

 

106

Spare

 

 

 

 

 

 

 

107

Spare

 

 

 

 

 

 

 

108

FP

R/W

 

HIA1

 

High Alarm AI1

 

 

109

FP

R/W

 

LOA1

 

Low Alarm AI1

 

 

110

FP

R/W

 

HIA2

 

High Alarm AI2

 

 

111

FP

R/W

 

LOA2

 

Low Alarm AI2

 

 

112

FP

R/W

 

HIA3

 

High Alarm AI3

 

 

113

FP

R/W

 

LOA3

 

Low Alarm AI3

 

 

114

FP

R/W

 

HIA4

 

High Alarm AI4

 

 

115

FP

R/W

 

LOA4

 

Low Alarm AI4

 

 

116

Byte

R/W

 

OCN1

 

Output #1 Configuration

 

 

 

B(1)

 

 

 

 

00001 Src of Module (Analog Items 1..31)

 

 

 



 

 

 

?.

 

 

 

B(5)

 

 

 

11111

 

 

 

B(6)

 

 

 

 

000 = Not used

 

 

 



 

 

 

 

001 = Output for Solenoids

 

 

 



 

 

 

 

010 = 0 to 10 V Analog Output

 

 

 



 

 

 

 

011 = ON/OFF Output

 

 

 



 

 

 

 

100 = DAT Output Type

 

 

 



 

 

 

 

101 = PAT Output Type

 

 

 

B(8)

 

 

 

 

110 = Multistage ON/OFF Type

 

 

117

FP

R/W

 

OCO1

 

PAT/DAT Timing for Output Module #1

 

 

118

Byte

R/W

 

OCN2

 

Output #2 Configuration

 

 

 

B(1)

 

 

 

 

00001 Src of Module (Analog Items 1..31)

 

 

 



 

 

 

?.

 

 

 

B(5)

 

 

 

11111

 

 

 

B(6)

 

 

 

 

000 = Not used

 

 

 



 

 

 

 

001 = Output for Solenoids

 

 

 



 

 

 

 

010 = 0 to 10 V Analog Output

 

 

 

B(8)

 

 

 

 

011 = ON/OFF Output

 

 

119

FP

R/W

 

OCO2

 

PAT Dead Band/Multistate Hysteresis #1

 

 

120

Byte

R/W

 

OCN3

 

Output #3 Configuration

 

 

 

B(1)

 

 

 

 

00001 Src of Module (Analog Items 1..31)

 

 

 



 

 

 

?.

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 43
Image 43
FieldServer FS-8700-19 PM5TYP, PM5K2, PM5K3, PM5K4, PM5K5, PM5K6, PM5K7, PM6K1, PM6TYP, PM6K2, PM6K3, PM6K4, PM6K5, PM6K6