FS-8700-19_Metasys_N2 Driver Manual

 

 

 

 

Page 30 of 51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Output Modules

 

 

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

 

Description

 

0

Byte

 

Write

DOT

 

Digital output options

 

1

Word

 

Write

DO@

 

Source of digital output module

 

2

Word

 

Write

FB@

 

Source of feedback signal

 

3

Word

 

Write

DOF@

 

Output forcing logic connection

 

4

FP

 

Write

HRO

 

Output high range

 

5

FP

 

Write

LRO

 

Output low range

 

6

FP

 

Write

FST

 

PAT output full stroke time/DAT cycle

 

7

FP

 

Write

DB

 

PAT deadband

 

8

FP

 

Write

HLO

 

Output high limit

 

9

FP

 

Write

LLO

 

Output low limit

 

10

FP

 

Write

OFL

 

Output % value in forcing mode

 

11

FP

 

Write

OUT

 

Output module output value %

 

12

Byte

 

Write

DOC

 

Logic output control and status

 

13

Word

 

Write

INC@

 

DDC increase logic connection

 

14

Word

 

Write

DEC@

 

DDC decrease logic connection

 

15

Word

 

Write

ENL@

 

Limit function enable logic connection

 

 

 

 

 

 

 

 

 

 

 

 

 

Extension Modules

 

 

 

Relative Item

Signal Condition

 

Read/Write

 

Johnson Tag

 

Description

 

0

Word

 

Write

 

XTIOMAP

 

Extension module I/O map

 

1

Word

 

Write

 

XTIOTYP

 

Extension module I/O type

 

2

Word

 

Write

 

XTIOMOD

 

Extension module I/O mode

 

3

Byte

 

Write

 

XTADX

 

Extension module address 0-255

 

4

Word

 

Write

 

XTI1@

 

Point connection - I1

 

5

Word

 

Write

 

XTI2@

 

Point connection - I2

 

6

Word

 

Write

 

XTI3@

 

Point connection - I3

 

7

Word

 

Write

 

XTI4@

 

Point connection - I4

 

8

Word

 

Write

 

XTI5@

 

Point connection - I5

 

9

Word

 

Write

 

XTI6@

 

Point connection - I6

 

10

Word

 

Write

 

XTI7@

 

Point connection - I7

 

11

Word

 

Write

 

XTI8@

 

Point connection - I8

 

12

FP

 

Write

 

XTHR01

 

High output range point 1

 

13

FP

 

Write

 

XTLR01

 

Low output range point 1

 

14

FP

 

Write

 

XTHR02

 

High output range point 2

 

15

FP

 

Write

 

XTLR02

 

Low output range point 2

 

16

FP

 

Write

 

XTHR03

 

High output range point 3

 

17

FP

 

Write

 

XTLR03

 

Low output range point 3

 

18

FP

 

Write

 

XTHR04

 

High output range point 4

 

19

FP

 

Write

 

XTLR04

 

Low output range point 4

 

20

FP

 

Write

 

XTHR05

 

High output range point 5

 

21

FP

 

Write

 

XTLR05

 

Low output range point 5

 

22

FP

 

Write

 

XTHR06

 

High output range point 6

 

23

FP

 

Write

 

XTLR06

 

Low output range point 6

 

24

FP

 

Write

 

XTHR07

 

High output range point 7

 

25

FP

 

Write

 

XTLR07

 

Low output range point 7

 

26

FP

 

Write

 

XTHR08

 

High output range point 8

 

27

FP

 

Write

 

XTLR08

 

Low output range point 8

 

28

FP

 

Write

 

XTHIA1

 

High alarm limit point 1

 

29

FP

 

Write

 

XTLOA1

 

Low alarm limit point 1

 

30

FP

 

Write

 

XTHIA2

 

High alarm limit point 2

 

31

FP

 

Write

 

XTLOA2

 

Low alarm limit point 2

 

32

FP

 

Write

 

XTHIA3

 

High alarm limit point 3

 

33

FP

 

Write

 

XTLOA3

 

Low alarm limit point 3

 

34

FP

 

Write

 

XTHIA4

 

High alarm limit point 4

 

35

FP

 

Write

 

XTLOA4

 

Low alarm limit point 4

 

36

FP

 

Write

 

XTHIA5

 

High alarm limit point 5

 

37

FP

 

Write

 

XTLOA5

 

Low alarm limit point 5

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 30
Image 30
FieldServer FS-8700-19 Dot, Do@, Fb@, Dof@, Fst, Doc, Xtiomap, Xtiotyp, Xtiomod, Xtadx, XTI1@, XTI2@, XTI3@, XTI4@, XTI5@