FS-8700-19_Metasys_N2 Driver Manual

 

 

 

 

 

 

 

Page 29 of 51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Programmable Module Type

 

 

 

 

 

Relative Item

Signal Condition

 

Read/Write

 

 

Johnson Tag

 

Description

 

57

FP

 

Write

 

 

PMK32

 

 

 

Module constant - K32

 

58

FP

 

Write

 

 

PMK33

 

 

 

Module constant - K33

 

59

FP

 

Write

 

 

PMK34

 

 

 

Module constant - K34

 

60

FP

 

Write

 

 

PMOU1

 

 

 

Output channel 1

 

61

FP

 

Write

 

 

PMOU2

 

 

 

Output channel 2

 

62

FP

 

Write

 

 

PMOU3

 

 

 

Output channel 3

 

63

FP

 

Write

 

 

PMOU4

 

 

 

Output channel 4

 

64

FP

 

Write

 

 

PMOU5

 

 

 

Output channel 5

 

65

FP

 

Write

 

 

PMOU6

 

 

 

Output channel 6

 

66

FP

 

Write

 

 

PMOU7

 

 

 

Output channel 7

 

67

FP

 

Write

 

 

PMOU8

 

 

 

Output channel 8

 

68

FP

 

Write

 

 

PMAX1

 

 

 

Auxiliary output 1

 

69

FP

 

Write

 

 

PMAX2

 

 

 

Auxiliary output 2

 

70

Byte

 

Write

 

 

PMHDC

 

 

 

Hold mode control/status

 

71

Byte

 

Write

 

 

PMDO

 

 

 

Logic output control and status

 

72

Word

 

Read

 

 

PMST

 

 

 

Programmable module status

 

73

LONG

 

Write

 

 

PMAC1

 

 

 

Accumulator channel 1

 

74

LONG

 

Write

 

 

PMAC2

 

 

 

Accumulator channel 2

 

75

LONG

 

Write

 

 

PMAC3

 

 

 

Accumulator channel 3

 

76

LONG

 

Write

 

 

PMAC4

 

 

 

Accumulator channel 4

 

77

LONG

 

Write

 

 

PMAC5

 

 

 

Accumulator channel 5

 

78

LONG

 

Write

 

 

PMAC6

 

 

 

Accumulator channel 6

 

79

LONG

 

Write

 

 

PMAC7

 

 

 

Accumulator channel 7

 

80

LONG

 

Write

 

 

PMAC8

 

 

 

Accumulator channel 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Input Modules

 

 

 

 

 

Relative Item

Signal Condition

 

Read/Write

 

Johnson Tag

 

 

Description

 

0

Word

 

Write

 

 

AIT

 

 

 

Analog inout type

 

1

FP

 

Write

 

 

HR

 

 

 

High range input

 

2

FP

 

Write

 

 

LR

 

 

 

Low range input

 

3

FP

 

Write

 

 

HIA

 

 

 

High alarm limit

 

4

FP

 

Write

 

 

LOA

 

 

 

Low alarm limit

 

5

FP

 

Write

 

 

FTC

 

 

 

Filter constant

 

6

FP

 

Write

 

 

ADF

 

 

 

Differential on alarm limit (units)

 

7

FP

 

Read

 

 

AI

 

 

 

Analog input value

 

8

FP

 

Read

 

 

AI%

 

 

 

Analog input %

 

9

FP

 

Read

 

 

ADC

 

 

 

Analog input in counts

 

10

Byte

 

Read

 

 

AIST

 

 

 

Analog input status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Output Modules

 

 

 

 

 

Relative Item

Signal Condition

Read/Write

 

Johnson Tag

 

Description

 

0

Byte

 

Write

 

AOT

 

Analog output type

 

1

Word

 

Write

 

AO@

 

Source of analog output module

 

2

Word

 

Write

 

AOF@

 

Output forcing logic connection

 

3

FP

 

Write

 

HRO

 

Output high range

 

4

FP

 

Write

 

LRO

 

Output low range

 

5

FP

 

Write

 

OFL

 

Output % value in forcing mode

 

6

FP

 

Write

 

OUT

 

Output module output value %

 

7

Byte

 

Write

 

AOC

 

Analog output control and status

 

8

FP

 

Write

 

HLO

 

Output high limit

 

9

FP

 

Write

 

LLO

 

Output low limit

 

10

Word

 

Write

 

INC@

 

DDC increase logic connection

 

11

Word

 

Write

 

DEC@

 

DDC decrease logic connection

 

12

Word

 

Write

 

ENL@

 

Limit function enable logic connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Output Modules

 

 

 

 

 

Relative Item

Signal Condition

Read/Write

 

Johnson Tag

 

Description