FS-8700-19_Metasys_N2 Driver Manual

 

 

 

 

 

Page 47 of 51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Output Config Parameters

 

 

 

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

 

 

162

FP

Write

 

WA

Winter Authority Slope

 

 

163

FP

Write

 

SA

Summer Authority Slope

 

 

164

Byte

R/W

 

FT@

Freeze Temperature connection

 

 

165

FP

Write

 

FSP

Freeze set point

 

 

166

FP

R/W

 

FDIF

Freeze Differential

 

 

167

Word

Write

 

LOO

Input/Output Override Control

 

 

 

W(1)

Read

 

 

Three Speed Fan Actual Speed

 

 

 



 

 

 

00 = Output OFF

 

 

 



 

 

 

01 = Speed #1

 

 

 



 

 

 

10 = Speed #2

 

 

 

W(2)

Read

 

 

11 = Speed #3

 

 

 

W(3)

 

 

 

Not used

 

 

 

 

W(4)

Read

 

FOS

Three spd Fan Overrd Reqst by Hardware

 

 

 

W(5)

Write

 

 

Fan Speed Reqst by Command Module

 

 

 



 

 

 

00 = Output OFF

 

 

 



 

 

 

01 = Speed #1

 

 

 



 

 

 

10 = Speed #2

 

 

 

W(6)

 

 

 

11 = Speed #3

 

 

 

W(7)

 

 

 

TM9100 Real Time Clk Refresh Request

 

 

 

W(8)

 

 

FOR

Three speed Fan Overrd Reqst Cmd Mod

 

 

 

W(9)

 

 

AIO1

Analog

Input #1 Override

 

 

 

W(10)

 

 

AIO2

Analog

Input #2 Override

 

 

 

W(11)

 

 

AIO3

Analog

Input #3 Override

 

 

 

W(12)

 

 

AIO4

Analog

Input #4 Override

 

 

168

Word

Write

 

CLACT

Control Loops Activity Mode

 

 

 

W(1)

Read

 

 

Loop #1 Heating

 

 

 

W(2)

Read

 

 

Loop #2 Heating

 

 

 

W(3)

Read

 

 

Loop #3 Heating

 

 

 

W(4)

Read

 

 

Loop #4 Heating

 

 

 

W(5)

Read

 

 

Loop #5 Heating

 

 

 

W(6)

Read

 

 

Loop #6 Heating

 

 

 

W(7)

 

 

 

Not used

 

 

 

 

W(8)

 

 

 

Not used

 

 

 

 

W(9)

Write

 

 

Loop #1 Active

 

 

 

 

W(10)

Write

 

 

Loop #2 Active

 

 

 

 

W(11)

Write

 

 

Loop #3 Active

 

 

 

 

W(12)

Write

 

 

Loop #4 Active

 

 

 

 

W(13)

Write

 

 

Loop #5 Active

 

 

 

 

W(14)

Write

 

 

Loop #6 Active

 

 

 

169

Word

R/W

 

ALG2

Configuration Index 2

 

 

170

FP

R/W

 

WAL

Winter Authority Limit

 

 

171

FP

R/W

 

SAL

Summer Authority Limit

 

 

 

 

 

 

 

 

 

 

 

Items Stored in the TM91xx External Database

 

 

 

Relative Item

Signal Condition

Read/Write

 

Johnson Tag

 

Description

 

 

 

256

Byte

Read

 

UNIT

 

Device Model : xxH

 

 

257

FP

Read

 

TEMP

 

Room Temperature

 

 

258

FP

Read

 

RSP

 

Remote Temperature Set Point

 

 

259

Word

Read

 

LOO

 

Copy of TC9100 Item LOO

 

 

260

Byte

Read

 

JMP

 

TM9100 Jumper Configuration & status

 

 

 

B(1)

 

 

JMP1

 

Clock Setting

Disable

 

 

 

B(2)

 

 

JMP2

 

Fan Setting

Disable

 

 

 

B(3)

 

 

JMP3

 

Time Schedule Setting Disable

 

 

 

B(4)

 

 

JMP4

 

Model with Time Schedule

 

 

 

B(5)

 

 

JMP5

 

Time Schedule Configuration Changed

 

 

261

Word

Write

 

TIME

 

Real Time

 

 

 

 

W(1)

 

 

 

 

RTC Minutes 0..59

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 47
Image 47
FieldServer FS-8700-19 Ft@, Fsp, Fdif, Loo, For, AIO1, AIO2, AIO3, AIO4, Clact, ALG2, Wal, Sal, Temp, Rsp, Jmp, JMP1, JMP2