Optimal start / stop module

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

0

Byte

Write

OSOPT

Module options

 

1

Word

Write

OSZT@

Zone temperature connection

 

2

Word

Write

OSOT@

Outdoor temperature connection

 

3

Word

Write

OSSP@

Zone temperature setpoint connection

 

4

Word

Write

OSOB@

Off setpoint bias connection

 

5

Word

Write

OSDI@

Disable module connection

 

6

Word

Write

OSDA@

Disable adaptive action connection

 

7

Word

Write

OSTS@

Connection at time schedule output

 

8

Word

Write

OSNX@

Connection at next output

 

9

Word

Write

OSTIM@

Connection at time to next output

 

10

FP

Write

OSPURGE

Minimum cool / heat time (min)

 

11

FP

Write

OSMAXST

Maximum start up time (min)

 

12

FP

Write

OSMAXSO

Maximum shut down time (min)

 

13

FP

Write

OSBHK

Start mode building heating factor

 

14

FP

Write

OSBCK

Start mode building cooling factor

 

15

FP

Write

OSSBHK

Stop mode building heating factor

 

16

FP

Write

OSSBCK

Stop mode building cooling factor

 

17

FP

Write

OSFW

Percentage adaptive control (filter weight)

 

18

FP

Write

OSHTD

Outdoor heating design temperature

 

19

FP

Write

OSCTD

Outdoor cooling design temperature

 

20

FP

Write

OSCRNG

Control range

 

21

FP

Write

OSSP

Zone temperature on setpoint

 

22

FP

Write

OSOB

Zone temperature off setpoint

 

23

FP

Write

OSTIM

Remaining time to next event

 

24

Byte

Write

OSSTA

Operating status