FS-8700-19_Metasys_N2 Driver Manual

Page 7 of 51

4.2.Client Side Connection Descriptions

 

Section Title

 

 

 

Connections

 

 

 

Column Title

Function

Legal Values

 

Port

Specify which port the device is

P1-P8, R1-R21

 

 

connected to the FieldServer

 

 

Protocol

Specify protocol used

Metasys_N2

 

Baud*

Specify baud rate

9600

 

Parity*

Specify parity

None

 

Data_Bits*

Specify data bits

8

 

Stop_Bits*

Specify stop bits

1

 

 

 

 

Handshaking*

Specify hardware handshaking

None

 

Poll _Delay*

Time between internal polls

0

 

Line_Drive_On*

Duration of RTS assert before

0.001s

 

start of transmission

 

 

 

 

Line_Drive_Off*

Duration of RTS assert after

0.000s

 

end of transmission

 

 

 

 

 

 

Example

 

 

//Client Side Connections

Connections

Port, Protocol

R1, Metasys_N2

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com