Appendix C.2. Hardware connections

The FS-8917-16 pigtail cable is typically used for this port arrangement. Connection is
depicted in the following diagram.
FS-8917-16
FS-X20
SERIAL
+
-
G
ORANGE/WHITE
(RJ45-08)
BROWN
(RJ45-01)
BLUE/WHITE
(RJ45-04)
RJ45 Male Modular
Jack
12345678
RJ45 Male Mo dular Jac k
12345678
RJ45 Fema le Mo dular Jack

Appendix C.3. Configuration Settings

The Port address in the Configuration needs to be set to R1 instead of P1.
Line_Drive_On and Line_Drive_Off need to be defined in the connections section of the
configuration file. These need to be set to at least 0.001s. Refer to Sections 4.2 and 5.1
for more information.