FS-8700-19_Metasys_N2 Driver Manual

 

 

 

 

Page 45 of 51

 

 

 

 

 

 

 

 

 

 

 

 

Input Output Config Parameters

 

 

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

 

 

 

W(14)

Read

 

Reset Cycle indication

 

 

 

W(15)

Read

 

00 = Power Up Reset

 

 

 



 

 

01

= External

Reset

 

 

 



 

 

10

= Oscillator Failure

 

 

 

W(16)

Read

 

11 = Watchdog Reset

 

 

133

Word

R/W

TCS2

TC9100 Controller Options

 

 

 

W(1)

 

 

00 Select Analog Input 1 ADC

 

 

 



 

 

to

 

 

 

 

 

 

W(2)

 

 

11 Select Analog Input 4 ADC

 

 

 

W(3)

 

 

TM9100 does not overrd the proc Variable

 

 

 

W(4)

 

 

Half

Alternate

Mode Timing

 

 

 

W(5)

 

 

0

=

Celsius

1 = Fahrenheit

 

 

 

W(6)

 

 

0 = 50 Hz 1 = 60 Hz Power Line

 

 

 

W(7)

 

 

Enable Facilitator Mode

 

 

 

W(8)

 

 

TRIAC7 is ON if mode is Comfort

 

 

 

W(9)

 

 

Digital Input #1 Mode

 

 

 



 

 

000

= Not used

 

 

 



 

 

001

= Window Open

 

 

 



 

 

010

= Occupancy Sensor

 

 

 



 

 

011

= Air Quality Sensor

 

 

 



 

 

100

= Reverse Action

 

 

 

W(11)

 

 

101

= Intrusion Alarm

 

 

 

W(12)

 

 

Negate Digital

Input #1

 

 

 

W(13)

 

 

Digital Input #2 Mode

 

 

 



 

 

000

= Not used

 

 

 



 

 

001

= Window Open

 

 

 



 

 

010

= Occupancy Sensor

 

 

 



 

 

011

= Air Quality Sensor

 

 

 



 

 

100

= Reverse Action

 

 

 

W(15)

 

 

101

= Intrusion Alarm

 

 

 

W(16)

 

 

Negate Digital

Input #2

 

 

134

Word

R/W

TCS3

Enable Jumper Options

 

 

 

W(1)

 

 

Enable Integral Zeroing Loop #1

 

 

 

W(2)

 

 

Enable Integral Zeroing Loop #2

 

 

 

W(3)

 

 

Enable Integral Zeroing Loop #3

 

 

 

W(4)

 

 

Enable Integral Zeroing Loop #4

 

 

 

W(5)

 

 

Enable Integral Zeroing Loop #5

 

 

 

W(6)

 

 

Enable Integral Zeroing Loop #6

 

 

 

W(7)

 

 

Not used

 

 

 

 

W(8)

 

 

Not used

 

 

 

 

W(9)

 

 

Enable Gain Doubling Loop #1

 

 

 

W(10)

 

 

Enable Gain Doubling Loop #2

 

 

 

W(11)

 

 

Enable Gain Doubling Loop #3

 

 

 

W(12)

 

 

Enable Gain Doubling Loop #4

 

 

 

W(13)

 

 

Enable Gain Doubling Loop #5

 

 

 

W(14)

 

 

Enable Gain Doubling Loop #6

 

 

135

Byte

Write

TCS1

Controller Options

 

 

 

B(1)

 

 

Not

used

 

 

 

 

B(2)

 

 

Not

used

 

 

 

 

B(3)

 

 

Not

used

 

 

 

 

B(4)

 

 

Not

used

 

 

 

 

B(5)

 

 

Not

used

 

 

 

 

B(6)

 

 

Not

used

 

 

 

 

B(7)

 

 

Not

used

 

 

 

 

B(8)

 

 

Default Action

1=Reverse

 

 

136

Word

R/W

HDW1

Hardware Configuration

 

 

137

FP

R/W

HRI1

High Range AI1

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 45
Image 45
FieldServer FS-8700-19 instruction manual TCS2, TCS3, TCS1, HDW1, HRI1