Input Output Config Parameters

 

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

 

138

FP

R/W

LRI1

Low Range AI1

 

 

139

FP

R/W

FTC1

Filter Constant AI1

 

 

140

FP

R/W

OFS1

Offset Compensation AI1

 

 

141

Byte

R/W

IOP1

Analog Input Options

 

 

 

B(1)

 

 

Controller reference

 

 

 



 

 

1 to 6

 

 

 

B(3)

 

 

 

 

 

 

 

B(4)

 

 

Input Type: 0=volt 1=resistance

 

 

 

B(5)

 

 

Input Mode

 

 

 



 

 

000 - Linear Range

 

 

 



 

 

001-Thermistor Linearization 2252.at 25C

 

 

 



 

 

010 - Square Root

 

 

 



 

 

011 - 0.2 suppression

 

 

 



 

 

100-Thermistor Linearization 10 k. at 25C

 

 

 

B(7)

 

 

101 - Square Root & 20 % suppression

 

 

 

B(8)

 

 

Not used

 

 

142

FP

R/W

HRI2

High Range AI2

 

 

143

FP

R/W

LRI2

Low Range AI2

 

 

144

FP

R/W

FTC2

Filter Constant AI2

 

 

145

FP

R/W

OFS2

Offset Compensation AI2

 

 

146

Byte

R/W

IOP2

Analog Input Options (see IOP1)

 

 

147

FP

R/W

HRI3

High Range AI3

 

 

148

FP

R/W

LRI3

Low Range AI3

 

 

149

FP

R/W

FTC3

Filter Constant AI3

 

 

150

FP

R/W

OFS3

Offset Compensation AI3

 

 

151

Byte

R/W

IOP3

Analog Input Options (see IOP1)

 

 

152

FP

R/W

HRI4

High Range AI4

 

 

153

FP

R/W

LRI4

Low Range AI4

 

 

154

FP

R/W

FTC4

Filter Constant AI4

 

 

155

FP

R/W

OFS4

Offset Compensation AI4

 

 

156

Byte

R/W

IOP4

Analog Input Options (see IOP1)

 

 

157

Byte

Write

OS

TC9100 Requested Operating Status

 

 

 

B(1)

 

 

00 = Night mode

 

 

 



 

 

01 = Stand-by mode

 

 

 



 

 

10 = Comfort mode

 

 

 

B(2)

 

 

11 = OFF mode

 

 

 

B(3)

 

 

Not

used

 

 

 

B(4)

 

 

Not

used

 

 

 

B(5)

 

 

Operating Mode Toggle: Base- Alternate

 

 

 

B(6)

 

 

Not

used

 

 

 

B(7)

 

 

Force Operating Mode

 

 

 

B(8)

 

 

Command Module Active

 

 

158

Word

Write

STIME

TM9100 Real Time Clk Synchronization

 

 

 

W(1)

 

RTC

Minutes 0..59

 

 

 



 

 

 

 

 

 

 

W(6)

 

 

 

 

 

 

 

W(7)

 

 

Spare

 

 

 

W(8)

 

 

Spare

 

 

 

W(9)

 

RTC

Hours 0..23

 

 

 



 

 

 

 

 

 

 

W(13)

 

 

 

 

 

 

 

W(14)

 

RTC

Day of Week 1..7

 

 

 



 

 

 

 

 

 

 

W(16)

 

 

 

 

 

 

159

Byte

R/W

OT@

Outdoor Temperature Connection

 

 

160

FP

Write

SPW

Winter set point

 

 

161

FP

Write

SPS

Summer set point

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 46
Image 46
FieldServer FS-8700-19 LRI1, FTC1, OFS1, IOP1, HRI2, LRI2, FTC2, OFS2, IOP2, HRI3, LRI3, FTC3, OFS3, IOP3, HRI4, LRI4, Rtc