FS-8700-19_Metasys_N2 Driver Manual

 

Page 27 of 51

 

 

 

 

 

 

 

 

 

General control module

 

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

0

Byte

Read

UNIT

Device model. For DX-9100 always 5

 

1

Word

Write

SUP

Supervisory central control

 

2

Byte

Read

MNT

Maintenance control

 

3

Word

Read

DIAG

Diagnistics

 

4

Byte

Read

DICT

Digital input counters

 

5

Byte

Read

TOS

Triac output status

 

6

Byte

Read

DIS

Digital input status

 

7

Word

Read

AIS

Analog input status

 

8

Word

Read

LRST1

Logic results 37637

 

9

Word

Read

LRST2

Logic results 17-32

 

10

Word

Write

LCOS1

Logic constants 37637

 

11

Word

Write

LCOS2

Logic constants 17-32

 

12

-

-

-

Spare

 

13

LONG

Write

CNTR1

DI1 pulse count

 

14

LONG

Write

CNTR2

DI2 pulse count

 

15

LONG

Write

CNTR3

DI3 pulse count

 

16

LONG

Write

CNTR4

DI4 pulse count

 

17

LONG

Write

CNTR5

DI5 pulse count

 

18

LONG

Write

CNTR6

DI6 pulse count

 

19

LONG

Write

CNTR7

DI7 pulse count

 

20

LONG

Write

CNTR8

DI8 pulse count

 

21

Word

Write

PASS

Password code

 

22

Byte

Write

PC1

Prescaler DI1 counter

 

23

Byte

Write

PC2

Prescaler DI2 counter

 

24

Byte

Write

PC3

Prescaler DI3 counter

 

25

Byte

Write

PC4

Prescaler DI4 counter

 

26

Byte

Write

PC5

Prescaler DI5 counter

 

27

Byte

Write

PC6

Prescaler DI6 counter

 

28

Byte

Write

PC7

Prescaler DI7 counter

 

29

Byte

Write

PC8

Prescaler DI8 counter

 

30

Byte

Write

UIA

User interface address

 

31

Word

Write

ALD@

Alarm disable condition source

 

32

Byte

Write

DXS1

DX-9100 type settings

 

33

Word

Write

ALG

Standard algorithm type

 

34

FP

Write

ACO1

Analog constant 1

 

35

FP

Write

ACO2

Analog constant 2

 

36

FP

Write

ACO3

Analog constant 3

 

37

FP

Write

ACO4

Analog constant 4

 

38

FP

Write

ACO5

Analog constant 5

 

39

FP

Write

ACO6

Analog constant 6

 

40

FP

Write

ACO7

Analog constant 7

 

41

FP

Write

ACO8

Analog constant 8

 

42

Byte

Write

PLCNT

PLC control and status

 

43

Word

Read

PLCPC

PLC program counter

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 27
Image 27
FieldServer FS-8700-19 Unit, Sup, Mnt, Diag, Dict, Tos, Dis, Ais, LRST1, LRST2, LCOS1, LCOS2, Long, CNTR1, CNTR2, CNTR3