FS-8700-19_Metasys_N2 Driver Manual

Page 40 of 51

Appendix D.3. Metasys TC9100 Memory Map

Note: The TC9100 is not currently supported by the FieldServer MetasysN2 Driver. The information below is for interest and future use only.

General dynamic Parameters

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

0

Byte

Read

UNIT

Device model. For TC-9100 always 06h

1

FP

Write

AI1

Process Temperature

2

FP

Write

AI2

Remote Temperature Set Point Bias

3

FP

Write

AI3

Pressure

 

4

FP

Write

AI4

Override Input

 

5

 

 

 

Spare

 

 

6

 

 

 

Spare

 

 

7

 

 

 

Spare

 

 

8

 

 

 

Spare

 

 

9

Word

Read

ADC

Selected Analog Input ADC counter

10

FP

Write

OCM1

Output Programmable Module #1

11

FP

Write

OCM2

Output Programmable Module #2

12

FP

Write

OCM3

Output Programmable Module #3

13

FP

Write

OCM4

Output Programmable Module #4

14

FP

Write

OCM5

Output Programmable Module #5

15

FP

Write

OCM6

Output Programmable Module #6

16

FP

Write

WSP1

Working Set Point Control Module 1

17

FP

Write

WSP2

Working Set Point Control Module 2

18

FP

Write

WSP3

Working Set Point Control Module 3

19

FP

Write

WSP4

Working Set Point Control Module 4

20

FP

Write

WSP5

Working Set Point Control Module 5

21

FP

Write

WSP6

Working Set Point Control Module 6

22

FP

Write

XAI1

External Analog Input 1

23

FP

Write

XAI2

External Analog Input 2

24

FP

Write

XAI3

External Analog Input 3

25

FP

Write

XAI4

External Analog Input 4

26

FP

Write

ACO5

Analog Constant 5

27

FP

Write

ACO6

Analog Constant 6

28

FP

Read

WAC

Winter Authority Correction

29

FP

Read

SAC

Summer Authority Correction

30

Word

Read

ALR

Analog Inputs Alarm Status

 

W(1)

 

AIH1

Analog

Input

1 High alarm

 

W(2)

 

AIL1

Analog

Input

1 High alarm

 

W(3)

 

AIH2

Analog

Input

2 High alarm

 

W(4)

 

AIL2

Analog

Input

2 Low alarm

 

W(5)

 

AIH3

Analog

Input

3 High alarm

 

W(6)

 

AIL3

Analog

Input

3 Low alarm

 

W(7)

 

AIH4

Analog

Input

4 High alarm

 

W(8)

 

AIL4

Analog

Input

4 Low alarm

 

W(9)

 

 

Not used

 

 

W(10)

 

 

Not used

 

 

W(11)

 

 

Not used

 

 

W(12)

 

 

Not used

 

 

W(13)

 

 

Not used

 

 

W(14)

 

 

Not used

 

 

W(15)

 

 

Not used

 

 

W(16)

 

 

Not used

 

31

Byte

Read

LOS

Logic Output Status

 

B(1)

 

DO3

TRIAC

3 ON

 

 

B(2)

 

DO4

TRIAC

4 ON

 

 

B(3)

 

DO5

TRIAC

5 ON

 