1750

Operators Manual

Specifications for the System: Recorder and Power Analyze Software

General Specifications

Power Quality Measurement Standards

 

Conformance

IEC 61000-2-4:2002 Class 1, IEC 61000-4-30, IEEE519, IEEE1159,

 

IEEE1459, IEC 61557-12:2008, and EN50160

Clock/Calendar

Leap years, 24-hour clock

Real-time Clock Accuracy

Not more than ± 1 s/day

Internal Memory Capacity for Data

At least 2 GB

Maximum Recording Period

At least 31 days

Measurement Time Control

Automatic

Maximum Number of Events

Limited only by the size of the internal memory.

Power Requirements

100 to 240 V rms ± 10 %, 47-63 Hz, 40 W

Operating Time During Interruptions

 

(internal UPS operation)

5 minutes per interruption, 60 minutes total operating time without

 

recharging

Dimensions

215 x 310 x 35 mm (8.5 x 12.2 x 3.5 inch)

Mass (Weight)

6.3 kg (14 lbs)

Input Specifications

Measurement Types

One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split

 

Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three

 

Phase High Leg, Three Phase Open Leg, 2 Element Delta, 2 ½

 

Element Wye

Input Channels

Voltage: 5 channels, AC/DC Current: 5 channels

Voltage Channels

Input resistance: 2 MΩ

 

Input capacitance: <20 pF

Current Channels

Self-identifying probes

 

Types available: current clamps, Flexi-CTs

Measuring Method

Simultaneous digital sampling of voltage and current. Digital PLL

 

synchronized sampling, internal frequency reference used during

 

voltage drops.

Synchronization and Sampling

PLL-Synchronization Source

The PLL synchronizes to the A-N/L1-N voltage for wye power types,

 

and to the A-B/L1-L2 voltage for delta power types. All listed power

 

types can be characterized as either wye or delta.

PLL Lock Range

42.5 to 69 Hz

Sampling Frequency

Voltage and current: 256 samples/cycle

 

Inter-harmonics per IEC61000-4-7: 2560 points / 10 cycles (50 Hz),

 

3072 points/12 cycles (60 Hz)

 

Transient Voltage: 5 MHz

A/D Resolution

Voltage and current: 24 bits

 

Transient voltage: 14 bits

Voltage and Current Measurements

Voltage Measurement Range

AC voltage: 1000 V rms ± 10 % Overrange

 

DC voltage: ± 1000 V + 10 % Overrange

Voltage Crest Factor

3 or less

Voltage Input Impedance

2 MΩ

Current Measurement Range

Depends on current probe used

Current Crest Factor

4 or less

Current Input Characteristics

2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low

 

impedance for Flexi-CTs

50

Page 58
Image 58
Fluke 1750 General Specifications, Input Specifications, Synchronization and Sampling, Voltage and Current Measurements