Power Recorder

 

Specifications for the System: Recorder and Power Analyze Software

 

Voltage and Current Measurement Accuracy

RMS Voltage

 

Measurement Type

True rms calculated continuously: every cycle, every 1/2 cycle, and

 

every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC

 

61000-4-30.

Measurement Uncertainty

AC: ± 0.2 % reading ± 0.1 % full scale above 50 V rms

 

DC: ± 0.5 % reading ± 0.2 % full scale above 50 V dc

 

If the ac component of a dc signal is below 40 V rms, the dc

 

uncertainty specification may have an offset.

RMS Current

 

Measurement Type

True rms calculated continuously: every cycle, every 1/2 cycle, and

 

every 10 or 12 cycles at 50 or 60 Hz respectively, as required by

 

standards

Measurement Uncertainty

± (0.1 % full scale + 0.5 % reading + current sensor accuracy, valid for

 

5 % to 100 % of current sensor range

Current Accuracy

Ferromagnetic Clamps

 

± (0.1 % full scale + 0.2 % reading + current sensor accuracy), valid for

 

5 % to 100 % of current sensor range

 

Flexible Current Probes

 

± (0.1 % full scale + 0.5 % reading + current sensor accuracy), valid for

 

5 % to 100 % of current sensor range

Transient Voltage (Impulse)

 

Measurement Type

Waveshape sampling, not peak detect

Full Scale

8000 V pk

Sample Resolution

200 nS

Measurement Uncertainty

± 5 % reading ± 20 V (test parameters: 1000 V dc, 1000 V rms,

 

100 kHz)

Dip (Sag) and Swell Measurements

Voltage Swell (rms swell)

 

Measurement Type

True rms (one cycle calculation by overlapping each half cycle)

 

(voltage between lines is measured for 3P3W lines and phase voltage

 

is measured for 3P4W lines)

Displayed Data

Amplitude and duration of swell

Measurement Accuracy

Same as rms voltage

Voltage Dip (RMS sag)

 

Measurement Type

True rms (one cycle calculation by overlapping each half cycle)

 

(voltage between lines is measured for 3P3W lines and phase voltage

 

is measured for 3P4W lines)

Displayed Data

Amplitude and duration of dip or interruption

Measurement Accuracy

Same as rms voltage

Voltage Dropout (Interruption)

 

Measurement Type

Same as Voltage Dip

Power and PF Measurement

Calculated per IEEE1459 for best performance when distortions exist

Measurement Type

True rms calculated continuously: every cycle, and every 10 or 12

 

cycles at 50 or 60 Hz respectively, as required by standards

Measurement Accuracy

± 0.2 % reading ± 0.1 % full scale + current sensor accuracy

Frequency

 

Measurement Range

42.5 to 69 Hz

Measurement Source

Same as PLL synchronization source

Measurement Accuracy

± 10 mHz (10 to 110 % of range, with sine wave)

Reactive Power

 

Accuracy

± 0.2% reading ± 0.1 % full scale + current sensor accuracy

51

Page 59
Image 59
Fluke 1750 Voltage and Current Measurement Accuracy, Transient Voltage Impulse, Dip Sag and Swell Measurements