Frymaster BIGLA30 warranty Danger, Gas Connection Pipe Sizes, or more, Single Unit, 2 - 3 Units

Models: BIGLA30

1 86
Download 86 pages 17.38 Kb
Page 14
Image 14
Gas Connection Pipe Sizes

4 or more DANGER

The appliance must be isolated from the gas supply piping system by closing its in- dividual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ PSI (3.45 kPa, 13.84 inches W.C.)

Single Unit DANGER

“Dry-firing” your unit will cause damage to the frypot and can cause a fire. Always ensure that cooking oil or water is in the frypot before firing the unit.

2 - 3 Units DANGER

All connections must be sealed with a joint compound suitable for the gas being used and all connections must be tested with a solution of soapy water before light- ing any pilots.

Never use matches, candles, or any other ignition source to check for leaks. If gas odors are detected, shut off the gas supply to the appliance at the main shut-off valve and immediately contact the local gas company or an authorized service agen- cy for service.

The size of the gas line used for installation is very important. If the line is too small, the gas pressure at the burner manifold will be low. This may cause slow recovery and delayed ignition. The incoming gas supply line should be a minimum of 1½” (38 mm) in diameter. Refer to the chart on the following page for the minimum sizes of connection piping.

Gas Connection Pipe Sizes

(Minimum incoming pipe size should be 1 1/2" (41 mm))

 

 

 

 

4 or more

Gas

Single Unit

2 - 3 Units

 

units*

Natural

3/4" (22 mm)

1" (28 mm)

1

1/4" (36 mm)

Propane

1/2" (15 mm)

3/4" (22 mm)

 

1" (28 mm)

Manufactured

1" (28 mm)

1 1/4" (36 mm)

1

1/2" (41 mm)

*For distances of more than 20 feet (6 m) and/or more than 4 fittings or elbows, increase the connection by one pipe size.

The BIGLA30 LOV™ gas fryer has received the CE mark for the countries and gas categories indicated in the table on the following page. NOTE: The nominal heat input (QN) is 21kW except for AT, DE, LU and category 3P/B, which is 23kW.

2-5

Page 14
Image 14
Frymaster BIGLA30 warranty Danger, Gas Connection Pipe Sizes, or more, Single Unit, 2 - 3 Units