5.1Electrical connections

WARNING!

All electrical connections must be made by a qualified electrician

and meet local electrical code standards

Before attempting to connect the mains supply, the reserve/bypass supply or the load, ensure that all supplies, including the battery, are isolated and that all the equipment switches are in their »OFF» position. Open UPS front access panel and remove internal panel over main switches and terminal blocks.

NOTES:

1)Installation must be performed by a qualified electrician. The terminals require the use of the proper crimp tools and terminals in order to perform an installation in accordance with the National Electrical Code (NEC). The recommended crimp tools, terminals and torque are shown in the following tables:

2)Use Copper Conductors Only

Table 1 – T&B’s Cat. N°s. for terminals and crimp tools

Wire

Terminals

 

Toggle

Size

Hole for screw

hand

(AWG)

M6

M10

 

8

D10711

 

D975

 

6

E10711

 

E975

 

4

F10711

 

F975

 

3

F10711

 

F975

 

2

G971

 

G974

WT117

1

G671

 

G974

 

1/0

H971

 

H974

 

2/0

J971

 

J974

 

3/0

K971

 

K974

 

4/0

L971

 

L974

 

Nest

(stationary)

tool

11803

11803

11805

11805

11806

11806

11807

11808

11809

11810

Indentor

(Moveable)

11802

 

 

Table 2 – Recommended torque

 

 

 

 

 

 

 

 

 

Type

Screw

 

Wrench

 

Torque

Used ON

 

 

 

(mm)

(Nm)

(lb.in)

 

 

 

 

 

 

 

 

Entrelec

 

 

 

 

 

EDP70Plus

M 35/26.FF

M6

 

10

4.5

39

 

up to 24kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

-------

M10

 

17

39

340

EDP70Plus

 

 

 

 

 

 

 

 

above 24kVA

 

 

 

 

 

 

 

page 32 --MI00/10056 rev. 8 —05/2006

Page 32
Image 32