Garmin EDP70 manual Connection, Uninterruptible Power System, No Unauthorized Operation

Models: EDP70

1 67
Download 67 pages 37.68 Kb
Page 30
Image 30
5.0CONNECTION

5.0CONNECTION

Protection devices to be installed by the customer according to the information shown on page 23

 

L1

UTILITY

L2

INPUT

L3

 

N

Neutral not present on

50 and 80kVA ratings

U2

L1

 

V2

L2

OUTPUT

W2

L3

 

N

N

(Neutral separately derived

U

 

on 50 and 80kVA ratings)

V

 

 

 

W

 

 

N

EXTERNAL

 

 

BATTERIES

2UNINTERRUPTIBLE POWER SYSTEMNO UNAUTHORIZED OPERATION Remove link to connect remote E.P.O.1

 

3

Battery Charge Inhibit

G

4

5

 

 

6

 

GROUND

Protection devices to be installed by the customer Manual backgroundaccording to the information shown on page 23

L1 RESERVE L2

INPUT L3 N

UTILITY L1L2 INPUT L3

U1

V1

W1

N Neutral not

present on

50 and 80kVA

ratings

U

V

W

U2

L1

 

V2

L2

OUTPUT

W2

L3

 

N

N

(Neutral separately derived

 

 

on 50 and 80kVA ratings)

 

EXTERNAL

 

BATTERIES

G

GROUND

1

2

3

4

5

6

Manual backgroundManual backgroundManual background Remove link to connect remote E.P.O.

Manual backgroundManual background Battery Charge Inhibit

Figure 17 – Connection diagrams

THE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH CIRCUIT PROTECTION.

NOTE:

INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN GROUND-NEUTRAL VOLTAGE TO AFFECT

 

THE LOAD.

NOTE:

ALL CIRCUIT BREAKERS OR FUSES AND ISOLATING SWITCHES SHOULD BE FITTED AS CLOSE TO THE EDP70

 

PLUS UPS AS POSSIBLE AND MARKED WITH THE LABELS PROVIDED WITH THE UNIT.

 

IT IS ALSO RECOMMENDED A LABEL AS FOLLOWS

 

 

 

 

 

 

UNINTERRUPTIBLE POWER SYSTEM

 

 

 

NO UNAUTHORIZED OPERATION

 

 

 

 

 

page 30 --MI00/10056 rev. 8 —05/2006

Page 30
Image 30
Garmin EDP70 manual Connection, Uninterruptible Power System, No Unauthorized Operation