S3 = Equipment By-pass switch

S4 = Equipment OUTPUT Breaker

S1 = Equipment ON/OFF Breaker

S2 = Equipment Reserve switch

Output, Input, Reserve

and External Battery Terminals

Access plate

Figure 22 - 36 – 24/30/36kVA: Connections

Access to the terminals for electrical connections is as follows:

a)Remove front panel see Figure 22.

b)Remove the terminal board compartment panel by unscrewing the fixing screws at the front.

c)This exposes the electrical terminal rail, see Figure 23

d)Remove the screws securing the access plate.

e)Push the interconnection cables up through the access plate.

f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked.

g)Install or start-up batteries see section 13.3 and 13.4.

h)Replace and tighten the terminal securing screws fully clockwise and refit the access plate.

i)Replace the terminal board compartment panel and the front cover.

OBSERVE POLARITIES AND ORIENTATIONS.

See Remote Alarms and Computer Interface for connections to these facilities.

MI00/10056 rev. 8 — 05/2006-- page 37

Page 37
Image 37
Garmin EDP70 manual 36 24/30/36kVA Connections