The measurement signals are accessed from the load output - reserve supply page as follows:

LOAD/RES ALARMS

NO ALARMS ACTIVE

press once

LOAD f xx.x Hz

A xxx V B xxx V C xxx V

press once

LOAD f xx.x Hz

AB xxx V BC xxx V CA xxx V

press once

LOAD

A xxx A B xxx A C xxx A

press once

LOAD

A x% B x% C x%

press once

LOAD P.F. 0.99

P = 80kW s = 80kVA

press once

RESERVE F xx.xHz

A xxx V B xxx V Cxxx V

press once

RESERVE F xx.xHz

AB xxx V BC xxx V CA xxx V

Normal operating mode

Displays the frequency and phase-neutral voltage supplied to the load.

Displays the frequency and phase-phase voltage supplied to the load.

Displays the current supplied to the load.

Displays the load capacity percentage of the UPS rated value.

Displays the Peak Factor of the load current.

Displays the frequency and phase-neutral voltage supplied to the reserve line.

Displays the frequency and phase-phase voltage supplied to the reserve line.

page 54 --MI00/10056 rev. 8 —05/2006