7.0START UP

1.Switch on the AC reserve and the main AC Utility supply to the UPS.

2.Turn on the Utility supply Input, Reserve Input (if fitted) and UPS Output switches located behind the front panel, see figure 18 for 24kVA, figure 21 for 36kVA or figure 24 for 50/80kVA.

3.Replace the front panel.

4.Press the CANCEL AUDIBLE ALARM switch (see section 6.2)

5.Initially, all the green indicators will flash on the display mimic. After about 30 seconds the supply and battery indicators should stop flashing.

6.Press the Inverter On push button (I).

7.The inverter should now start and after a delay of approximately 30 seconds the message ‘SYSTEM NORMAL’, in English, will appear on the liquid crystal display.

8. Select the required language by pressing page right control

until the ‘SELECT LANGUAGE’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

message appears on the liquid crystal display. Press the page down control

 

 

until the required

 

 

 

once more confirm the language selection.

 

 

language is selected. Press the page right control

 

Thereafter, all messages will appear in the selected language.

 

 

 

 

 

8.0MAINTENANCE BYPASS

The EDP70 PLUS UPS is equipped with Manual Maintenance Bypass systems. If a unit requires servicing, the Manual Maintenance Bypass allows the load to be connected directly to the AC supply so that the unit may be serviced in safety. The following instructions must be followed:

1.Ensure that ‘SYSTEM NORMAL’ is displayed on the LCD. (Note: If ‘SYSTEM NORMAL’ is not displayed check that the inverter is not ‘OUT OF SYNC’, see section 10.7. Turning the inverter off under this fault condition will interrupt the load supply.)

2.Turn off the inverter by pressing the inverter shutdown button for more than 2 seconds

3.Turn the Maintenance Bypass Switch (located behind front panel, see figure 18, 21 or 24) to ON.

4.Turn off the Primary Input, Reserve Input and UPS Output Switches, see figure 18, 21 or 24.

THE LOAD IS NOW SUPPLIED DIRECTLY FROM THE AC UTILITY SUPPLY AND IS NO LONGER PROTECTED BY THE UPS

CAUTION: Some components in the UPS will retain a static voltage even after the switches have been opened. Also, on the 50/80kVA ratings, the isolating transformer and the relative cooling fans are still supplied from the Bypass.

To return to the normal operating mode, follow the above procedure in reverse.

Note: The EDP70 PLUS UPS must not be left operating with the Maintenance Bypass Switch in the ON position.

MI00/10056 rev. 8 — 05/2006-- page 45

Page 45
Image 45
Garmin EDP70 manual Maintenance Bypass