4.2Installation

Check the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/output voltages, frequency and load are all within the rating of the UPS.

EDP70 PLUS is designed to operate in an office environment with an optimum temperature of 68°F [20 C]. A gap of at least 4 in [ 10cm. ] must be maintained at rear of the UPS to ensure adequate ventilation. Nothing should be placed around the equipment which might restrict the airflow.

Ensure the interconnecting cables do not cause a hazard to the user.

A gap of at least 32 in [ 812 mm] must be maintained above the UPS to ensure adequate space for maintenance. The appropriate lifting equipment must be used to move the EDP70 PLUS UPS.

Figure 16 – UPS Ratings

 

 

 

 

UPS ratings

 

 

 

 

 

 

 

 

 

 

 

Description

U.M.

24

24

24

 

36

36

36

 

 

12kVA

18kVA

24kVA

 

24kVA

30kVA

36kVA

 

 

 

 

 

 

 

 

 

Output power

kVA

12

18

24

 

24

30

36

 

 

 

 

 

 

 

 

 

Nominal Load

kW

8

12

16

 

16

20

24

 

 

 

 

 

 

 

 

 

Maximum input power (with

 

 

 

 

 

 

 

 

unit @ nominal Load & battery

kVA

15

21

28

 

28

35

42

recharge)

 

 

 

 

 

 

 

 

Maximum dissipation (with

BTU/H

3750

5460

6800

 

7700

9500

11300

inverter @ nominal Load)

 

 

 

 

 

 

 

 

Number of battery cells

n

 

144

 

 

 

240

 

 

 

 

 

 

 

 

 

 

Battery voltage range

V

 

238-327

 

 

 

396-545

 

 

 

 

 

 

 

 

 

 

Battery

A

37

55

74

 

53

67

80

end-discharge current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS ratings

 

 

 

 

 

 

 

 

 

 

Description

U.M.

50

50

50

 

80

80

80

 

 

30kVA

40kVA

50kVA

 

50kVA

65kVA

80kVA

 

 

 

 

 

 

 

 

 

Output power

kVA

30

40

50

 

50

65

80

 

 

 

 

 

 

 

 

 

Nominal Load

kW

24

32

40

 

40

52

64

 

 

 

 

 

 

 

 

 

Maximum input power (with

 

 

 

 

 

 

 

 

unit @ nominal Load & battery

kVA

43

57

71

 

71

91

112

recharge)

 

 

 

 

 

 

 

 

Maximum dissipation (with

BTU/H

9300

11700

14300

 

14300

18600

22100

inverter @ nominal Load)

 

 

 

 

 

 

 

 

Number of battery cells

n

 

 

 

240

 

 

 

 

 

 

 

 

 

Battery voltage range

V

 

 

396-545

 

 

 

 

 

 

 

 

 

 

Battery

A

67

88

110

 

105

140

173

end-discharge current

 

 

 

 

 

 

 

 

page 26 --MI00/10056 rev. 8 —05/2006