Reserve Supply

AC Supply

S3

Maintenance By-pass

S2

 

S1

S4

Battery

24/36kVA Ratings

Contactor

S3

Reserve Supply S2

S1

AC Supply

Maintenance By-pass

S5

480Y/277V

 

S4

208Y/120V

Battery

Contactor 50/80kVA Ratings

Figure 5 – Re-establishing the Utility Supply

When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times.

S3

Reserve Supply

S2

S1

AC Supply

Maintenance By-pass

S4

Battery

Contactor 24/36kVA Ratings

 

S3

Reserve Supply

S2

 

S1

AC Supply

 

 

Maintenance By-pass

 

S5

 

480Y/277V

 

S4

 

208Y/120V

Battery

50/80kVA Ratings

Contactor

Figure 6 – Transferring the Load onto the Reserve Supply

Transfer onto the reserve line is caused by two conditions:

a)inverter stop

b)overload

In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as the it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents.

MI00/10056 rev. 8 — 05/2006-- page 13

Page 13
Image 13
Garmin EDP70 manual Contactor 24/36kVA Ratings