#10 Self-Drill

4” Vent Pipe

Screws

(horizontal position)

(typical)

 

Flue Adapter

Collar

2” (5cm) Clearance Thimble

1/2” (12mm) fall per 20 ft (6m) toward vent terminal

6” (15cm) minimum

Vent Cap (Breidert or equivalent Type L)

MULTIPLE HEATER VENTING (CONNECTIONS INTO A COMMON VENT OR MANIFOLD)

Requirements for venting of multiple heaters are the same as described for SINGLE HEATER VENTING except as follows:

1.The common vent size and total vent height is normally determined by the number of heaters per common vent, length of horizontal connector runs, and connector rise. Connector lengths should be as short as possible and have a minimum 1/2 inch per 20 foot fall. Without regard to connector rise and total vent height due to many possible venting configurations, the following should be observed:

a.Common vent pipe & vent connector diameter should be no less than that shown in the following Vent Sizing Table.

b.The connector length should be no more than 75% of the vertical portion of vent above the connector.

c.Where possible, use a Y-connector to the common vent.

2.Material for connectors should be constructed of galvanized sheet metal or other approved noncombustible corrosion resistant material as allowed by state or local codes. All common vent pipe should be double wall, Type B vent.

3.Avoid unnecessary bends. Limit to two (2) 90º elbows.

4.The entire length of vent connector shall be readily accessible for inspection, cleaning and replacement.

5.Groups of heaters with a common vent must be controlled by a common thermostat.

Multiple Heater Vertical venting arrangement.

Vent Cap (Leslie

VersaCap Type B)

Flashing

Total

Vent 2” (5cm)

Height Clearance

Thimble

Seal Joint

and Annular

Space

Plan View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 ft (77cm) minimum

 

 

 

 

 

 

 

 

 

 

 

 

(when no wall or

 

 

 

 

 

 

 

 

 

parapet exists)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 ft

(77cm)

 

 

10 ft (305cm)

 

 

 

minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vent size table

Wallor Parapet

 

 

 

 

 

See multiple

 

 

 

 

 

 

 

 

 

 

 

 

for diameter

4” Diameter single wall Vent

Flue Collar

adaptor

Connections to the common vent must be arranged to avoid direct opposition of exhaust products.

 

Form #43343530

–36–

JJuly 08

Page 37
Image 37