2.0INSTALLATION
The following installation guidelines will help you install your new
2.1Feed Water Requirements
The following feed water requirements must be met before installing your new
Table 2.4
Feed Water Requirements
Temperature | Typical: 10 - 29°C (50° - 85°F) |
Inlet Pressure | Minimum: 2.1 barg (30 psig) |
| Maximum: 4.1 barg (60 psig) |
|
|
Chlorine (continuous feed) | 0 ppm |
|
|
Feed Water | For soft water [less than 1 grain per gallon |
| (gpg) or 17 mg/L hardness] |
| acceptable pH: 3.0 - 11.0 |
|
|
| For unsoftened water (contact factory for |
| water analysis), acceptable pH: 5.0 - 6.0 |
|
|
| For |
| SDI range: 2 - 12 |
Silt Density Index | Less than or equal to 4 to minimize mem- |
(SDI) | brane element fouling and extend cleaning |
| intervals. Refer to ASTM Standard |
| D4189 |
2.2Mounting