Section 6.3

ENGINE CRANKING SYSTEM

BATTERY (CONTINUED)

1.Set the VOM to its "Rx1 " scale and zero the meter.

2.Connect the VOM test leads across the Wire 17 terminal and

TESTING A BATTERY:

The best method of testing a battery is with an auto- motive type battery hydrometer. Some "Maintenance Free" batteries cannot be tested with a hydrometer.

Most batteries can be tested for both STATE OF CHARGE and CONDITION as follows:

1.Test for State of Charge:

a.Follow the hydrometer manufacturer's instruc- tions carefully. Test the specific gravity of the fluid in all battery cells.

b.If the hydrometer does not have a "Percentage of Charge" scale, compare the readings obtained with the following:

SPECIFIC GRAVITY PERCENTAGE OF CHARGE

the center (Wire 0) terminals.

a. Hold the switch at "START" and the VOM should indicate "continuity".

b. Hold switch at "STOP" and meter should read "infinity".

3.Now, connect the meter test leads across the center and Wire 18 terminals.

a.With switch at "START" VOM should indicate "infinity".

b.With switch at "STOP", meter should read "con- tinuity".

Replace the switch if it is defective.

1.260

100%

1.230

75%

 

 

1.200

50%

 

 

1.170

25%

If the battery State of Charge is less than 100%, use an automotive type battery charger to recharge it to a 100% State of Charge.

2.Test for Condition:

a.If the difference in specific gravity between the highest and lowest reading cell is greater than 0.050 (50 points), the battery is nearing the end of its useful life and should be replaced.

b.However, if the highest reading cell is less than 1.230, recharge the battery and repeat the test.

START-RUN-STOP SWITCH (SW1)

Wires 17 and 18 connect to the two outer terminals of the switch. Wire 0 (ground) connects to the switch center termi- nal. The switch can be tested using a volt-ohm-milliamme- ter (VOM) as follows:

Figure 2.

STARTER CONTACTOR

WIRE AND CABLE CONNECTIONS:

The red (positive) battery cable connects to one of the starter contactor's large terminal lugs. The unit's 15 amp fuse also attaches to this lug, via Wire 13.

The starter motor (SM1) cable (16) attaches to the second terminal lug.

Wire 56, from the A6060 circuit board, attaches to one of the small contactor terminals.

TESTING THE STARTER CONTACTOR:

To test the installed Starter Contactor, proceed as fol- lows:

1.Set a volt-ohm-milliammeter (VOM) to read battery voltage (12 VDC).

2.Connect the VOM test leads across the Wire 56 terminal of the Contactor and frame ground. The meter should indicate "zero" volts.

3.Hold the Start-Run-Stop switch at "START" and the VOM should read battery voltage and the Contactor should energize. After reading the voltage, release the switch. If battery voltage is NOT indicated, a problem exists elsewhere in the circuit.

4.Connect the VOM test leads across the Wire 16 terminal lug and frame ground.

a.Hold the Start-Run-Stop switch at "START". The Contactor should actuate and the meter should indicate battery voltage.

b.If battery voltage is not indicated, replace the Starter Contactor.

c.If battery voltage is indicated but engine does not crank, check the Starter Motor and its cable.

Page 6.3-2

Page 96
Image 96
Generac Power Systems 940-2, 941-2 service manual Battery, START-RUN-STOP Switch SW1, Starter Contactor

941-2, 940-2 specifications

Generac Power Systems has established a strong reputation in the field of backup power solutions, particularly with its innovative products like the Generac 940-2 and 941-2 generator systems. These generators are designed to provide reliable power during emergencies, ensuring that homes and businesses can maintain operations seamlessly when grid power is disrupted.

One of the standout features of the Generac 940-2 and 941-2 models is their robust engine performance. Both generators utilize Generac’s patented engines, known for their durability and efficiency. These engines are built to withstand the most demanding conditions while providing a consistent power output. This reliability is crucial for users who depend on uninterrupted power supply for essential appliances and equipment.

In terms of technologies, the Generac 940-2 and 941-2 are equipped with advanced automatic transfer switch capabilities. This technology allows the generators to automatically start and supply power within seconds of an outage. This quick response time helps to ensure that critical systems remain operational without noticeable interruptions, which is vital for businesses and households alike.

Another important characteristic of these models is their user-friendly interface. The generators come with an intuitive digital controller that provides real-time information on power usage, system status, and maintenance needs. This technology makes it easy for users to monitor their generators and ensure they are always ready for an emergency.

The design of the Generac 940-2 and 941-2 also emphasizes noise reduction and aesthetic appeal. These units are engineered for quieter operation compared to traditional generators, making them suitable for residential areas. Their sleek appearance also fits well with modern home exteriors, enhancing rather than detracting from the property’s visual appeal.

Furthermore, these generators offer flexible fuel options, with the ability to run on natural gas or propane. This versatility allows users to choose the fuel source that best meets their needs, contributing to energy efficiency and lowering overall operating costs.

In summary, the Generac Power Systems 940-2 and 941-2 are exceptional generators that combine powerful performance with innovative technologies. Their automatic transfer switch capabilities, user-friendly controls, noise reduction features, and flexible fuel options make them an excellent choice for anyone seeking reliable backup power solutions. With these generators, users can rest assured knowing they have a dependable energy source ready when they need it most.