Section 7.2

ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

TEST 11- TEST STARTER CONTACTOR

DISCUSSION:

See "Starter Contactor" on Page 6.3-2. Replace Starter Contactor if bad.

TEST 12- TEST START-STOP SWITCH

DISCUSSION:

Engine cranking and startup are initiated when the Start-Stop switch is held at "START" to ground Wire 17.

Engine shutdown is normally initiated when the Start- Stop switch is set to "STOP" to ground Wire 18.

A defective switch can prevent normal startup or nor- mal shutdown.

Figure 7. Start-Stop Switch

TEST PROCEDURE:

1.Carefully inspect Wire 0 (Ground) between the Start-Stop switch and the ground terminal. Repair, reconnect or replace the wire if necessary.

2.Disconnect Wire 17 from its terminal on the Start-Stop switch. Connect Wire 17 to a clean frame ground. The engine should crank.

3.Start the engine, using the Start-Stop switch or by grounding Wire 17.

4.Stop the engine by holding the Start-Stop switch at "STOP". If engine will not shut down with switch at "STOP", ground Wire 18 to stop engine.

RESULTS:

1.If engine cranks when Wire 17 is grounded, but won't crank with Start-Stop switch, replace the Start-Stop switch.

2.If engine stops when Wire 18 is grounded but will not shut down with Start-Stop switch, replace the Switch.

3.If engine will not crank when Wire 17 is grounded, replace the A6060 circuit board.

4.If engine will not stop when Wire 18 is grounded, replace the A6060 circuit board.

TEST 13- CHECK FUEL SUPPLY

DISCUSSION:

If the engine cranks but won't start, don't overlook the obvious. The engine won't start without fuel.

TEST PROCEDURE:

Check fuel level.

RESULTS:

1.If fuel level is low, replenish fuel supply.

2.If fuel quantity is good, go to Test 14.

TEST 14- CHECK FUEL FILTER

Refer to Section 3.3.

TEST 15- CHECK IGNITION SPARK

Refer to Section 6.4, "ENGINE IGNITION SYSTEM".

TEST 16- CHECK SPARK PLUG

DISCUSSION:

A badly fouled spark plug can prevent the engine from starting. A defective spark plug may allow the engine to be started, but rough operation or an "engine miss" may be observed.

A commercially available spark tester can be used to check for ignition spark. When the spark tester is con- nected in series with the spark plug and its high ten- sion lead, the cause of an engine miss can be nar- rowed down to either (a) the ignition system, or (b) the spark plug or fuel system. Use of the spark tester is discussed in Test 16.

TEST PROCEDURE:

Remove the spark plug.

Clean by scraping or wire brushing and by using a commercial solvent. DO NOT BLAST CLEAN THE PLUG. Set spark plug gap to 0.030 inch (0.76mm). Replace spark plug if badly fouled, if ceramic is cracked, or if damaged.

Page 7.2-13

Page 123
Image 123
Generac Power Systems 941-2 Test 11- Test Starter Contactor, Test 12- Test START-STOP Switch, Test 13- Check Fuel Supply

941-2, 940-2 specifications

Generac Power Systems has established a strong reputation in the field of backup power solutions, particularly with its innovative products like the Generac 940-2 and 941-2 generator systems. These generators are designed to provide reliable power during emergencies, ensuring that homes and businesses can maintain operations seamlessly when grid power is disrupted.

One of the standout features of the Generac 940-2 and 941-2 models is their robust engine performance. Both generators utilize Generac’s patented engines, known for their durability and efficiency. These engines are built to withstand the most demanding conditions while providing a consistent power output. This reliability is crucial for users who depend on uninterrupted power supply for essential appliances and equipment.

In terms of technologies, the Generac 940-2 and 941-2 are equipped with advanced automatic transfer switch capabilities. This technology allows the generators to automatically start and supply power within seconds of an outage. This quick response time helps to ensure that critical systems remain operational without noticeable interruptions, which is vital for businesses and households alike.

Another important characteristic of these models is their user-friendly interface. The generators come with an intuitive digital controller that provides real-time information on power usage, system status, and maintenance needs. This technology makes it easy for users to monitor their generators and ensure they are always ready for an emergency.

The design of the Generac 940-2 and 941-2 also emphasizes noise reduction and aesthetic appeal. These units are engineered for quieter operation compared to traditional generators, making them suitable for residential areas. Their sleek appearance also fits well with modern home exteriors, enhancing rather than detracting from the property’s visual appeal.

Furthermore, these generators offer flexible fuel options, with the ability to run on natural gas or propane. This versatility allows users to choose the fuel source that best meets their needs, contributing to energy efficiency and lowering overall operating costs.

In summary, the Generac Power Systems 940-2 and 941-2 are exceptional generators that combine powerful performance with innovative technologies. Their automatic transfer switch capabilities, user-friendly controls, noise reduction features, and flexible fuel options make them an excellent choice for anyone seeking reliable backup power solutions. With these generators, users can rest assured knowing they have a dependable energy source ready when they need it most.