Low Level Filtering Screen Setup

The Low Level Filtering screen setup is used to filter out spurious signals from rotating paddle type low level sen- sors.

NOTE: When using the GLC4400 with the G3 Automatic Lubrication Pump, it is recommended that the low level filtering be set to G3 defaults.

The NUMBER field determines how many signal activa- tions are required to set a fault.

The TIME field determines the amount of RUN time required without an activation to reset the activation count to 0 (zero).

8.Use the RIGHT arrow to move the cursor to the next field. Repeat step 7.

9.Repeat steps 7 and 8 until the desired time is dis- played.

10.Press ENTER.

11.If the default values for the G3 Automatic Lubrica- tion Pump are intended to be used, use the UP/DOWN arrows to move to the G3 DEFAULT field.

12.Press ENTER. The NUMBER and TIME values will be updated to the G3 default value.

13.Press RESET. The Main Screen, shown on page 18, displays.

FIG. 52

1.Use the Arrow keys to move the cursor over the NUMBER field.

2.Press ENTER.

3.Use the UP/DOWN arrows to move up and down through the numbers 0-9 until the first number you want in the NUMBER field is displayed.

4.Use the RIGHT arrow to move the cursor to the next field. Repeat step 3.

NOTE: The maximum number of Counts you can setup in this field is 99.

5.Use the Arrow keys to move the cursor over the TIME field.

6.Press ENTER.

NOTE: Time is displayed in HH:MM:SS.

7.Use the UP/DOWN arrows to move up and down through the numbers 0-9 until the first number in the TIME field is displayed.