Installation procedure | Install indoor unit |
1.Before installation [Before finishing installation, do not throw the attached parts installation needs]
Confirm the way to move the unit to the installation place.
Before moving the unit to the installation place, do not remove their packages. When have to remove the package, use a soft material or protection board with rope to lift the unit assembly to avoid unit damage or bumping a scrape.
2.Choose installation place
(1)The chosen installation place should meet the following requirements and get the user’s consent.
Place ensures ideal airflow distribution. The passage of airflow has no obstacles.
The condensate water can be drained smoothly. Place can stand the weight of indoor unit. Place ensures enough space for maintenance.
The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation part).
The indoor unit, outdoor unit, electric wire and connection wire is at least
1m away from television and radio. This is to avoid the image disturbance and noise caused by the
(2)The height of ceiling
The indoor unit can install on the ceiling, which height is no more than 2.7m. (3)Install and use the hoisting screw. Check if the installation place can bear the
weight of unit assembly. If not certain, strengthen it before install the unit. (The installation gaps are marked on the installation paper panel. Refer to the paper panel to find those points needing to fixing.)
280 |
|
|
|
|
Ceiling |
|
| Over 1500 |
|
|
|
|
| |
Over 1500 | Over1000 |
| Air |
|
groundthe |
|
|
| |
Air |
| Air inlet | discharging |
|
discharging |
|
| hole | Over 1500 |
hole |
|
| ||
|
|
| ||
from | Obstacle |
|
| |
Not exceeding 2700 |
|
| ||
|
|
| Over 1500 |
Space installation needed (unit: mm)
Over 1500
Over 1500
23