Installation procedure | Install indoor unit |
Original cement panel
Use the in hole hinge, in hole plug or in hole screw.
Steel structure
Directly use angle steel or new angle steel for support.
Suspending of indoor unit
Suspending bolt
Hoisting screw | Angle steel for support |
Adjust the position of screw cap (underside) to make the gap between the attached washer (underside) and the ceiling is 135mm.
*.Installation of indoor unit
M10 screw
135mm
Ceiling
Hoisting screw
Screw cap (upside)
Attached washer
(The suspending part of the unit)
Screw cap (underside)
Tighten the screw cap of the hoisting screw and suspend them on the T groove of the unit suspending part.
Use gradienter to keep the level degree of the unit within 5mm.
Use installation paper panel to confirm and adjust the position relation between unit and ceiling opening and the suspending height of the unit. (shows the using direction of the installation paper panel)
*The bottom of indoor unit is 43mm away from the bottom of ceiling. (4 corners)
*The side of the indoor unit leaves 25mm gaps from ceiling.
4 edges together
The fittings should be prepared on site except for M10 flat washer
Gradienter
Suspending bolt (M8 or M10)
Screw cap (M8 or M10)
M10 or M8 flat washer
Hoisting screw
Suspending pole
M10 or M8 flat washer
In order to prevent the bolt from breaking off (safety), they must be installed blow the sus pending parts as this figure shown.
Screw cap (M8 or M10)
Indoor unit | 43mm |
| |
Ceiling | Installation paper panel 25mm |
|
25