Hose
Indoor unit
Accessorial thermal insulation material

Installation procedure

Install indoor unit

Manual background The indoor side drain hose and the parts connected with indoor unit should be thermal insulated. Improper thermal insulation may cause dew-forming phenomenon.

Manual background The drain hose should be as short as possible. The droop slant degree at least should be 1/100 to avoid forming of gas bag.

Manual background If cannot make the drain hose have an enough slant degree, a drainage enhancing hose should be equipped.

Manual background In order not to let the drain hose bend, a 1~1.5m distance should be kept between suspending frame.

1m*1.5m

 

 

 

***

 

As large as possible (about 10cm)

Droop slant degree over

S-shaped bend

 

VP30

1/100 Support frame

 

 

Droop slant degree over

Thermal insulation material

 

1/100 Support frame

 

 

 

(customer self-provided)

 

Hose

Hose buckle

Thermal insulation treatment:

Manual background Use thermal insulation material, as figure shown, to bind the hose and the hose buckle to the bottom of the indoor unit without any gaps.

Hose

The hose can be used to adjust the radius and angle of stiff PVC pipe. *Directly stretch the hose to perform work, do not make it deform. *The soft end of the hose must be fixed by the hose buckle.

*Please use the hose in the level part.*

Stiff PVC pipe

Thermal insulation material

Radius adjustment

 

(Max 20mm)

20mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45* bend(Max)

 

 

 

 

 

 

Hose buckle

Manual background Hose

Hose

<The attentive matters of drainage enhancing pipe>

Manual background The installation height of the drainage enhancing pipe should be less than 530mm.

Manual background The drainage enhancing pipe should be vertical to the unit and no more than 300mm away from the unit.

Within 300mm 1-1.5mHoisting foot

Drain hose

220530Below

750Below

(accessory)

Drainage enhancing pipe

 

Drain hose (accessory)

Below 75

Below 750

Wire clamp (accessory)

Instruction)

*The slant of the accessory drain hose should be within 75mm to make the drain faucet not bear too much excessive external force.

*If many drain hoses join together, please install according to the following procedure.

Over 100

T-joint joined drain hose

The specification of the chosen joined drain hoses should be applicable to the operation capacity of the unit. 27