Installation procedure
Install indoor unit
The indoor side drain hose and the parts connected with indoor unit should be thermal insulated. Improper thermal insulation may cause
The drain hose should be as short as possible. The droop slant degree at least should be 1/100 to avoid forming of gas bag.
If cannot make the drain hose have an enough slant degree, a drainage enhancing hose should be equipped.
In order not to let the drain hose bend, a 1~1.5m distance should be kept between suspending frame.
1m*1.5m |
|
|
|
*** |
| As large as possible (about 10cm) | |
Droop slant degree over |
| VP30 | |
1/100 Support frame |
| ||
| Droop slant degree over | ||
Thermal insulation material |
| 1/100 Support frame | |
|
|
| |
(customer |
| Hose | Hose buckle |
Thermal insulation treatment:
Use thermal insulation material, as figure shown, to bind the hose and the hose buckle to the bottom of the indoor unit without any gaps.
Hose
The hose can be used to adjust the radius and angle of stiff PVC pipe. *Directly stretch the hose to perform work, do not make it deform. *The soft end of the hose must be fixed by the hose buckle.
*Please use the hose in the level part.*
Stiff PVC pipe
Thermal insulation material
Radius adjustment |
|
(Max 20mm) | 20mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
45* bend(Max) |
|
|
|
|
|
| Hose buckle |
Hose
Hose
<The attentive matters of drainage enhancing pipe>
The installation height of the drainage enhancing pipe should be less than 530mm.
The drainage enhancing pipe should be vertical to the unit and no more than 300mm away from the unit.
Within 300mm | ||
Drain hose | 220530Below | 750Below |
(accessory) | Drainage enhancing pipe |
|
Drain hose (accessory)
Below 75 | Below 750 |
Wire clamp (accessory)
Instruction)
*The slant of the accessory drain hose should be within 75mm to make the drain faucet not bear too much excessive external force.
*If many drain hoses join together, please install according to the following procedure.
Over 100
The specification of the chosen joined drain hoses should be applicable to the operation capacity of the unit. 27