2.4temperature level control 2.4.1 Deviation

 

 

 

 

 

HSU-12HS03/R2(DB)

 

 

 

 

 

 

 

 

 

Domestic Air Conditioner

Models: HSU-09HS03/R2(DB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and medium of wind volume when it is under heating mode. Modification index table for set temperature

Mode

Content of modification

Modified variable

Modified parameter

 

 

 

 

Heating

Operation mode modi hp

ETBL0

 

 

fication

 

 

 

 

 

 

 

Forceful operation modification

ETBL1

 

 

 

 

 

 

Weak wind volume

ETBL2

 

 

modification

 

 

 

 

 

 

 

Medium wind volume

ETBL3

 

 

modification

 

 

 

 

 

 

Cooling &

Operation mode modification

ETBL4

 

moisture

 

 

 

Forceful operation modification

ETBL5

 

removing

 

 

 

 

 

 

 

2.4temperature level control 2.4.1 Deviation

Work out the deviation of temperature level as follows:

In heating mode: E=(Remote -control set temperature+ modified value)-room temperature

In cooling & moisture removing mode: E= room temperature -(Remote-control set temperature + modified value)

2.4.2 Compressor OFF

E is minus and E>ΔT

 

Heating

 

Cooling

 

 

 

 

 

ΔT

TCHAHL

 

TCHACL

 

afterΔT changes

TCHAHH

 

TCHACH

 

condition forΔT changes

 

 

 

 

 

 

 

 

 

The compressor stops after 120 seconds of continuous detection

When the operation starts,according to the table above, the unit will operate according to the after-the-ΔT-change parameters before the compressor stops for the first time.

From the time the compressor stops to the time it starts again, the operation will follow the ΔT (except the moisture removing mode)

When the operation starts and the operation modes change (except when the idle mode is over) and the deviation is bigger than ΔT, the compressor starts.

When the compressor is working and the remote -controller set temperature falls below ΔT, the compressor stops.

2.4.3 Compressor operation

When the compressor is kept idle for 3 minutes, the deviation E will be higher than -T+0.67and the compressor will start working.

2.4.4 DASH operation

When the operation starts or the operation mode changes (except when the compressor is switched on after being off), the compressor is on and the indicated maximum frequency should be as follows:

24