Domestic Air Conditioner

HSU-12HS03/R2(DB)

Model: HSU-09HS03/R2(DB)

OUTDOOR UNIT PART

Chapter I: Indoor Unit and Main board for Outdoor Unit

Notice:

During operations under any mode, if short circuit, open circuit and other malfunctions of the temperature sensors are detected, the main engine should come to a halt immediately.

1. Outdoor-board:

1.1.Forced cooling operation switch:

Short circuit this switch before electrifying, data communication to indoor unit will be ignored:

Forced cooling will function, the 3-minute delay will be cancelled, and the following output will be ON simultaneously:

High wind volume (H) for outdoor fan motor; Compressor operates at the frequency of 80Hz.

1.2.Forced heating operation switch:

Short circuit this switch before electrifying, data communication to indoor unit will be ignored:

Forced heating will function, the 3-minute delay will be cancelled, and the following output will be ON simultaneously:

High wind volume (H) for outdoor fan motor; Compressor operates at the frequency of 80Hz. CPU checks all A/D ports

BWhen safeguarding action happens outdoors, the actions in A should be OFF, and other inputs are independent of the actions in A.

CLED output: Goes along even if safeguarding action happens outdoors; Cut this switch and go back to the original state. (The out-door safeguarding action will continue)

Chapter II: Basic Functions

3. Cooling mode

3.1.The four-way valve does not work (not electrified)

3.2.The discharge temperature sensor will not be tested within five minutes after the compressor is started

3.3.Outdoor fan motor control: The fan motor starts five seconds after the compressor starts, switching conditions for the two gears of wind volume are

as follows:

 

T ambient temp. <21

, Low wind volume

 

 

 

 

 

 

 

 

T

ambient

temp.

>21 , High wind

volume

 

 

When the fan motor starts up, and

the ambient temperature is at the return difference ( 2

), it runs at the low

 

 

 

 

 

± ℃

 

wind volume.

 

 

 

 

 

 

 

3.4.Compressor control: Frequency range: 30HZ---------

120HZ

frequency is

 

T ambient temp. <16

, the maximum

65HZ

16

 

 

30

the maximum

℃≤

T ambient temp.

 

 

 

 

≤ ℃,

frequency is 90HZ

T ambient temp. 41

 

the maximum frequency is

30

 

 

℃≤

 

℃,

 

 

110HZ

 

 

 

 

 

 

 

 

℃,

 

 

 

 

T ambient temp.

41

the maximum frequency is 85HZ

Actual temperature and frequency maybe adjusted through EEPROM

34

Page 34
Image 34
Haier HSU-09HS03/R2DB, HSU-12HS03/R2DB service manual Outdoor Unit Part