D.Conditions to exit the defrosting stage
outdoor coil57, the

Domestic Air Conditioner

HSU-12HS03/R2(DB)

Model: HSU-09HS03/R2(DB)

halts during the defrosting stage, remain still for 30 seconds, then conducts defrosting operation if it is still within the defrosting stage, the compressor starts according to the demand of the startup of the defrosting compressor.

Entering into the defrosting stage, it must be guaranteed that the minimum operation time of the compressor should amount at least to 2 minutes before exit defrosting.

D.Conditions to exit the defrosting stage

The defrosting operation will return to heating operation if any of the following conditions is met.

1):The temperature of the outdoor heat exchanger remains above 7 (Can be adjusted through EEPROM) for over 80 seconds continuously.

2):Keep defrosting operation for 9 minutes (Can be adjusted through EEPROM) continuously.

EAfter the condition to exit defrosting operation is met, work as

follows.

The compressor stops, the outdoor fan motor stops 50 seconds later, the four-way valve turns on, the compressor starts according to the starting process.

Time sequence of the defrosting operation is as follows: Compressor

Outdoors fan motor

Four-way valve

60×9Max

5.Outdoor condensation temperature control while cooling:

5.1.When the operation frequency F40HZ, if the temperature of the outdoor coiled pipe T outdoor coil52, decrease the operation frequency of the compressor by 2Hzthen examine the temperature of the outdoor coiled pipe at 10-second intervals, if T outdoor coil52, decrease the operation frequency further by 2Hzuntil the frequency is the lowest;

During the frequency-decreasing operation, if 47℃ ≤ T outdoor coil 52 , the compressor and the fan motor keep their original states;

the compressor runs at the normal operating frequency, and the outdoor fan motor returns to its original state,

5.2.When the operation frequency F40HZ, if the temperature of the outdoor coiled pipe T outdoor coil57, decrease the operation frequency of the compressor by 2Hzthen examine the temperature of the outdoor coiled pipe at 10-second intervals, if T outdoor coil57, decrease the operation frequency further by 2Hzuntil the frequency is the lowest;

During the frequency-decreasing operation, if 52℃≤T compressor and the fan motor keep their original states;

When T outdoor coil51, the compressor runs at the normal operating frequency,

36