Domestic Air Conditioner | |
Model: |
4.Heating mode
4.1.The
4.2.Malfunctions of the discharge temperature sensor will not be tested within five minutes after the compressor is started
4.3.Outdoor fan motor control: The fan motor starts five seconds after the compressor starts, switching conditions for the two gears of wind volume are
as follows: | T ambient temp. | <16 ℃ , | High | wind |
volume | T ambient | temp. ≥ 16 ℃ , Low | ||
wind volume | When the | fan | motor |
starts up, and the ambient temperature is at the return difference (±2℃), it runs at the low wind volume.
4.4.Compressor control: Frequency range:
T ambient temp. >22℃, the maximum frequency is 70HZ
9℃≤T ambient temp.≤22℃,the maximum frequency is 90HZ 2 ℃ ≤ T ambient temp.≤9℃,the maximum frequency is
100HZ
T ambient temp. <2℃,the maximum frequency is 110HZ
Actual temperature and frequency can be adjusted through EEPROM 4.5.Conditions to enter into the defrosting stage:
A. Conditions to enter into the defrosting stage
After the heating operation has begun, and the operation time of the compressor adds up to 45 minutes (The total operation time of the compressor will be reset to zero after defrosting or the operating mode switched into cooling), through examining the defrosting sensor TE (Examining the frosting status of the outdoor heat exchanger) and the ambient temperature sensor TA, if the following conditions are met continuously up to 5 minutes, then defrosting operation is entered:
TE≤C×TA-α
Of which:C:TA<0℃,C=0.8 TA≥0℃,C=0.3
αmaybe adjusted through EEPROM
For places easy to frost, set α as H; For places not easy to frost, set α as L; It is set as M when leaving factory.
Temperature limit to enter into the defrosting stage
B.Time interval of defrosting
•While the calculated data of C×TA-α fall within the range of
•While the calculated data of C×TA-α fall within the range of C×TA-α
C.Defrosting operation
•When defrosting begins, the compressor and the outdoor fan motor stops, and the
•The compressor starts and stays at the frequency of 60HZ for 30 seconds, then operates towards the target frequency (Can be adjusted through
EEPROM)
•The current safeguard and the compressor discharge safeguard and other means of safeguard remain valid while defrosting. If the compressor