Haier HSU-12HS03/R2DB Purging Method To use vacuum pump, Outdoor Unit, Domestic Air Conditioner

Models: HSU-12HS03/R2DB HSU-09HS03/R2DB

1 65
Download 65 pages 35 Kb
Page 63
Image 63
Outdoor Unit

Domestic Air Conditioner

HSU-12HS03/R2(DB)

Model: HSU-09HS03/R2(DB)

Outdoor Unit

5 Purging Method: To use vacuum pump

Liquid Side

Gas Side

 

 

6.35mm(1/4")

9.52mm(3/8")

 

 

12.7mm(1/2")

Detach the service port's cap of 3-way ,the

2-way valve

3-way valve

valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of change hose (low) for gaugemanifold. Then connect the projection of change hose (center) for gaugemanifold into vacuum pump.

5 Purging Method: To use vacuum pumpManual background Gaugemanifold(for R410A)

Manual background Anti countercurrent joint

Tube(for R410A)

Vacuum pump(for R410A)

Open the handle at low in gaugemanifold, operate

vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check Manual background again.

Open

Vacuumize for over 15min. And check the level gauge

 

which should read -0.1MPa (-76cmHg) at low

 

pressure side. After the completion of vacuumizing.

 

close the handle 'Lo' in gaugemanifold and stop the

Close

operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min.

If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of Manual backgroundManual background

Open the valve rod for the 2-way valve to an angle of

 

 

 

anti-clockwise 90 degrees.

 

3-way valve

After 6 seconds, close the 2-way valve and make the

2-way valve

 

Service port

inspection of gas leakage.

 

 

Open

 

for 6 sec.

 

 

 

 

 

If it does not stop gas leakage, discharge

 

In case of gas leakage, tighten

whole refrigerants from the service port.

No gas leakage?

parts of pipe connection. If

After flaring work again and vacuumize,

fill up prescribed refrigerant from the gas

leakage stops, then proceed

 

cylinder.

 

 

 

steps.

 

 

 

 

 

 

Detach the charge hose from the service port, open

 

 

 

2-way valve and 3-way. Turn the valve rod anti-clockwise

 

 

3-way valve

until hitting lightly.

 

2-way valve

 

 

 

 

To prevent the gas leakage, turn the service port's

 

 

 

cap, the valve rod's cap for 2-way valve and 3-way's

 

 

 

a little more than the point where the torque increases

2-way valve

 

3-way valve

suddenly.

 

 

 

 

 

 

 

 

Valve rod cap

After attaching the each caps, check the gas leakage

Service port cap

Valve rod cap

 

around the caps.

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to discharge the refrigerant out. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.

2.Please do not let other cooling medium, except specified one (R410A), or air enter into the cooling circulation system. Otherwise, there will be abnormal high pressure in the system to make it crack and lead to personal injuries.

63